Safety Data Sheet
®
DuPont
Suva
410A Refrigerant
Version 2.0
Revision Date 03/23/2015
Environmental precautions
Spill Cleanup
Accidental Release Measures
SECTION 7. HANDLING AND STORAGE
Handling (Personnel)
Handling (Physical Aspects)
Dust explosion class
Storage
Storage period
Storage temperature
SECTION 8. EXPOSURE CONTROLS/PERSONAL PROTECTION
Ref. 130000050990
: Should not be released into the environment.
In accordance with local and national regulations.
: Evaporates.
Ventilate area using forced ventilation, especially low or enclosed places
where heavy vapors might collect.
: Avoid open flames and high temperatures. Self-contained breathing
apparatus (SCBA) is required if a large release occurs.
: Avoid breathing vapours or mist. Avoid contact with skin, eyes and clothing.
Provide sufficient air exchange and/or exhaust in work rooms. For personal
protection see section 8.
: The product should not be mixed with air for leak testing or used with air for
any other purpose above atmospheric pressure. Contact with chlorine or
other strong oxidizing agents should also be avoided.
: Not applicable
: Valve protection caps and valve outlet threaded plugs must remain in place
unless container is secured with valve outlet piped to use point. Do not drag,
slide or roll cylinders. Use a suitable hand truck for cylinder movement. Use a
pressure reducing regulator when connecting cylinder to lower pressure
(<3000 psig) piping or systems. Never attempt to lift cylinder by its cap. Use a
check valve or trap in the discharge line to prevent hazardous back flow into
the cylinder. Cylinders should be stored upright and firmly secured to
prevent falling or being knocked over.
Separate full containers from empty containers. Keep at temperature not
exceeding 52°C. Do not store near combustible materials. Avoid area where
salt or other corrosive materials are present.
The product has an indefinite shelf life when stored properly.
: > 10 yr
: < 52 °C (< 126 °F)