Retardo Encendido Entre Dos Compresores/Parcializaciones; Retardo Apagado Entre Dos Compresores/Parcializaciones - Carel uC2 Manual Del Usuario

Tabla de contenido

Publicidad

- Retardo de arranque entre compresores
c04: Establece el retardo entre los arranques de dos compresores,
para reducir la entrada de pico de corriente y hacer que los com-
presores arranque más suavemente. El LED del compresor par-
padea en esta fase.
En el caso de control de capacidad, el retardo c04 entre el
compresor y la válvula se convierte en c04/2;
En el caso del funcionamiento de desescarche, el retardo
entre compresor y compresor es de 3 segundos, y entre el
compresor y la válvula es de 2 segundos.
Comando 1
1st Signal
Comando 2
2nd Signal
Compresor 1
1st Compressor
Compresor 2
2nd Compressor
- Retardo de parada entre compresores
c05: Establece el retardo de parada entre compresores.
Comando 2
2nd Signal
Comando 1
1st Signal
Compresor 2
2nd Compressor
Compresor 1
1st Compressor
- Retardo al conectar la tensión (reset tensión de alimentación)
c06: Al conectar la tensión (cuando el controlador se enciende física-
mente) se retrasa la activación de todas las salida con el fin de
distribuir la entrada de tensión y proteger al compresor contra
los arranques repetidos que se pueden producir en el caso de
que haya frecuentes cortes de corriente. Esto significa que
después del tiempo de retardo, el controlador comenzará a
gestionar las salida en función de los tiempos y las otras funcio-
nes normales.
C4

Retardo encendido entre dos Compresores/parcializaciones

Time-delay between two compressors ON routines/time-delay
of the capacity-controlled routine
Fig. 5.5
C5

Retardo apagado entre dos compresores/parcializaciones

Time-delay between two compressors OFF routines/time-delay
before the capacity-controlled routine is OFF
Fig. 5.6
44
- Start delay between compressors
c04: This sets the delay between the starts of the two compressors, so
as to reduce the peak power input and make the compressors start
more smoothly. The compressor LED flashes in this phase.
In the event of capacity control, the delay c04 between compressor
and valve becomes c04/2;
In the event of defrost operation, the delay between compressor and
compressor is 3 seconds, and between compressor and valve is 2
seconds.
- Stop delay between compressors
c05: This sets the stop delay between the compressors.
- Delay on power-up (reset power supply)
c06: At power ON (when the controller is physically switched ON) the
activation of all the outputs is delayed so as to distribute the
power input and protect the compressor against repeated starts in
the event of frequent power failures. This means that after the
delay time, the controller will start to manage the outputs based
on the other times and the other normal functions.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
- cod. +030220420 - rel. 2.1 - 17.01.05
µC
2

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido