PROBLEM
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A39, A40
AND THE RED
"REPLACE BATTERIES"
LED IS ON
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F34, L34, L35, L36
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F37, L37
THE DISPLAY IS BLANK
OR GIVES INCORRECT
INFORMATION
THE DISPLAY AND THE
FANS ARE OFF BUT THE
LOAD IS POWERED
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F48, L48
POSSIBLE CAUSE
THE BATTERIES HAVE NOT
PASSED THE PERIODIC
EFFICIENCY CHECK
▪
AMBIENT TEMPERATURE
GREATER THAN 40°C
▪
HEAT SOURCES IN THE
PROXIMITY OF THE CPS
▪
VENTILATION SLITS
BLOCKED OR TOO
CLOSE TO THE WALLS
MALFUNCTIONING OF
THE TEMPERATURE
SENSOR OR THE CPS
COOLING SYSTEM
▪
AMBIENT TEMPERATURE
GREATER THAN 40°C
▪
HEAT SOURCES IN THE
PROXIMITY OF THE CPS
▪
AIR SLITS BLOCKED OR
TOO CLOSE TO THE
WALLS
▪
MALFUNCTIONING OF
THE TEMPERATURE
SENSOR OR THE
BATTERY CHARGER
COOLING SYSTEM
THE DISPLAY HAS POWER
SUPPLY PROBLEMS
DUE TO MALFUNCTIONING
OF THE POWER SUPPLIES,
THE CPS IS IN BYPASS
MODE, SUPPORTED BY THE
REDUNDANT POWER SUPPLY
BATTERY ANTI-INVERSION
SYSTEM FAILURE OR
INCORRECT BATTERY
POLARITY
It is advisable to replace the batteries in the battery rack
as they are no longer able to maintain their charge for a
sufficient period of autonomy.
Caution: The batteries must only be replaced by
qualified personnel.
Activate the maintenance bypass (SWMB) without
switching off the CPS; in this way, the fans cool the
heat sink more quickly. Remove the cause of the
overtemperature and wait until the heat sink
temperature decreases. Exclude the maintenance
bypass.
Activate the maintenance bypass (SWMB) without
switching off the CPS so that the fans cool the heat sink
more quickly by continuing to operate. Switch the CPS
off and back on again. Exclude the maintenance
bypass. If the problem persists, call the nearest
assistance centre.
Remove the cause of the overtemperature.
Open the battery rack switch/fuse and wait until the
battery charger heat sink temperature decreases.
Close the battery fuse holder. If the problem occurs
again,
contact
the
CAUTION: never open the SWBATT fuse holders
during battery operation.
Close Manual Bypass (SWMB) keeping closed INPUT
and OUTPUT switches.
Open input switch (SWIN and SWBYP) and wait until
CPS is completely turned OFF.
Turn ON SWIN and SWBYP again and verify display
regular operation. Exclude the maintenance bypass. If
the fault persists, contact the nearest technical support
centre.
Activate the maintenance bypass (SWMB). Open the
input isolating switch, wait for a few seconds and close
SWIN again.
Try to switch the CPS on again.
If the display does not come back on or the sequence
fails, contact the nearest assistance centre, leaving the
CPS in manual bypass mode.
Check the battery polarity. Contact the support centre if
the error persists.
105
SOLUTION
nearest
assistance