Ocultar thumbs Ver también para Saturn:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

CPS models
Input stage
Rated voltage
Nominal voltage
Max input current
Max battery current
Accepted input tolerance range in order to
prevent battery intervention (refers to 400Vac)
Accepted input tolerance range in order to
prevent battery intervention (refers to
50/60Hz)
Cut-in threshold in Emergency Only mode
and for EOS
Cut-in time in Emergency Only mode
Input current harmonic distortion
Input power factor
Power Walk-In
Output stage
(1)
Rated voltage
(2)
Nominal voltage
Output current
Rated apparent output power
Rated active output power
Output power factor
Short circuit current
Output voltage precision (refers to 400Vac
output voltage)
(3)
Static stability
Dynamic stability
Output voltage harmonic distortion with
standardised linear and distorting load
Crest factor allowed at rated load
Frequency precision in free running mode
Inverter overload (Vin>345V AC )
Bypass Overload
Battery charger stage
Rated voltage
Maximum recharging current
Input voltage tolerance range for recharging
at maximum current

TECHNICAL DATA

(5)
CPS 100
380-400-415 Vac three-phase with neutral (4 wire)
50-60Hz
185 A
254 A
20% @ 100% load
-40% +20% @50% load
20%
40-72Hz
- 20% of nominal voltage
< 300ms
THDi  4 %
≥0.99
Can be programmed from 5 to 30 sec in 1 sec stages.
380/400/415 Vac three-phase with neutral (4 wire)
50/60Hz
152 A
100kVA
90kW
0.9
1.5x Ir for t>500ms
 1%
 0.5%
 3% resistive load
2% with linear load
4% with distorting load
3:1
0.01%
120% Infinite, 130% 10 min, 160% 1 min
130% Infinite,160% 60 minutes, 180% 10 minutes
240Vdc
25A
345-480Vac
110
(7)
(4)

Publicidad

Tabla de contenido

Solución de problemas

loading