EDUNDANT AUXILIARY POWER SUPPLY FOR AUTOMATIC BYPASS
The CPS is equipped with a redundant auxiliary power supply which allows operation on the automatic bypass in the
event of a fault with the main auxiliary power supply. In the event of a fault with the CPS which also leads to the
breakage of the main auxiliary power supply, the load nevertheless remains powered through the automatic bypass. The
multiprocessor board and the control panel are not powered therefore the LEDS and the display are off.
E
XTERNAL TEMPERATURE SENSOR
This NON-ISOLATED input can be used to measure the temperature inside the battery rack.
The use of the temperature sensor allows the CPS control logic to regulate the load voltage values and keep the battery
working temperature constant.
It is necessary to use the specific kit supplied by the manufacturer only: any uses which do not comply with the
specifications may cause malfunctioning or breakage to the appliance.
For installation, connect the cable contained in the specific kit to the "EXT BATTERY TEMP PROBE" connector (see "Ext
connection view" ).
After installation, enable the outdoor temperature measuring function using the configuration software.
R
EMOTE PANEL
The remote panel allows the CPS to be monitored from a distance and the user to have a detailed overview of the state
of the machine in real time. Using this device, it is possible to keep the electrical mains, output and battery
measurements etc, under control and to detect any alarms.
For details relative to use and connection, refer to the specific manual.
(
)