OWER WALK
IN
The CPS is equipped with a Power Walk-In mode which can be activated and configured via configuration software.
When this mode is enabled, once the mains power is restored (after a period of autonomy), the CPS begins absorbing
from it again progressively so as not to threaten (due to the peak) for any generator group that may be installed
upstream. The duration of the transition can be set from 0 to 125 seconds. The default value is 10 seconds (when this
function is active). During the transition, the power required is drawn partly from the batteries and partly from the mains
while maintaining sinusoidal absorption. The battery charger is switched back on only after the transition is complete
R
(
200V
208V)
EDUCING THE LOAD
AT
AND
In the event that the output voltage between phase and neutral is set at 200V and 208V (see "CPS configuration"
paragraph), the maximum power which can be supplied by the CPS is subject to a reduction compared to the rated
power, as shown below: