6.2 Minimum distances

Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due
to overheating.
► Keep the ventilation slots clear.
► Ensure sufficient distance to neighboring components.
► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
To the base of the control cabinet
To the roof of the control cabinet
Between the device and other assem-
blies on offset cap rails
Table 3: Minimum clearances in the control cabinet
Figure 11: Minimum clearances
For other installation types, contact Maschinenfabrik Reinhausen GmbH.

6.3 Assembly variants

6.3.1 Flush panel mounting

The device can be mounted in a control panel using tension clamps. The
recommended wall thickness is 2...5 mm.
Minimum clearance: 88.9 mm (3.5 in)
88.9 mm (3.5 in)
AVR STATUS
ALARM
REMOTE
ENTER
AVR AUTO
AVR MANUAL
BACK
88.9 mm (3.5 in)
7820658/01 EN
6 Mounting
Equivalent to 2RU
Maschinenfabrik Reinhausen GmbH 2021