6 Mounting
Cable
Power supply (external)
Voltage measurement
Current measurement
Digital signal inputs
Digital signal outputs
Analog signal inputs
RS232, D-SUB 9-pole
RS485
CAN bus
Ethernet RJ45
Ethernet FO
110 V DC output
RJ45 patch cables
Table 4: Recommendation for connection cables
6.4.2.1 Wiring requirement of installation site
Maschinenfabrik Reinhausen GmbH 2021
Excessive line capacitance can prevent the relay contacts from interrupting
the contact current. In control circuits operated with alternating current, take
into account the effect of the line capacitance of long control cables on the
function of the relay contacts.
If you want to route Ethernet connections from a control cabinet or building,
we recommend using fiber-optic cables (in accordance with the
IEC 61850-90-4 recommendation).
Interface
Cable type
X9
Unshielded
UI-X7
Shielded
UI-X7
Unshielded
DI 8
Shielded
DI 8
Shielded
AI 4
Shielded
X3
Shielded
X5
Shielded
COM-X6
Shielded
COM-X6
Min. CAT5, shielded
COM-X4
Duplex LC multi-
mode, Om3,
1,310 nm
X8
Unshielded
Min. CAT5, shielded
*) Observe line capacitance, see note above.

6.4.2 Electromagnetic compatibility

The device has been developed in accordance with applicable EMC stan-
dards. The following points must be noted in order to maintain the EMC
standards.
Note the following when selecting the installation site:
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
7820658/01 EN
Conductor cross-sec-
tion
1.5 mm²
2.5 mm²
4 mm²
1.5 mm²
1 mm²
0.25 mm²
0.25 mm²
0.75 mm²
S/FTP
1.5 mm²
S/FTP
Max. length
400 m (<25Ω/km)
400 m (<25Ω/km)
25 m
140 m
2,000 m (total CAN bus)
100 m
2,000 m
approx. 30 cm
®
TAPCON
230
33