6.4.10 Wiring resistor contact series
6.4.11 Connecting the power supply
Miniature circuit breaker You must fuse the power supply circuit with a miniature circuit breaker. The
Conductor cross-section For the power supply circuit, use a conductor cross-section suitable for the
®
46
TAPCON
230
6.4.9 Wiring digital outputs DO
DO 8
Figure 34: Block diagram for digital outputs
1. Feed the wires into the terminal of the plug connection diagram [►Section
10.14, Page 67] and fasten them using a screwdriver.
2. Plug the connector into the respective slot and screw it into place.
Connect the resistor contact series to the COM X6 and AI 4 interfaces in ac-
cordance with the connection diagram.
You may only connect the device to circuits with an external overcurrent pro-
tective device and an all-pole isolating device, allowing the equipment to be
fully de-energized if required (service, maintenance etc.).
Suitable equipment includes isolating devices in accordance with
IEC 60947-1 and IEC 60947-3 (e.g. circuit breakers). Observe the properties
of the relevant circuits (voltage, maximum currents) when selecting the cir-
cuit breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and the circuits to be
isolated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor
miniature circuit breaker must have the following properties:
▪ Rated current: 16...20 A
▪ Triggering characteristic: C, K or Z
miniature circuit breaker that you have selected, but at least 1.5 mm
15).
CAN bus
Controller
Reinforced
insulation
U+
U-
1-pole with
1-pole with connected
connected
positive
negative
R z
7820658/01 EN
6 Mounting
2-pole
R z
R z
Maschinenfabrik Reinhausen GmbH 2021
2
(AWG