Electrical Connection - Sime Estelle B4 INOX ErP Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para Estelle B4 INOX ErP:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 17
– 0.024 for light oil
– 0.016 for gas
P boiler input in kcal/h
H height of flue in meters, meas-
ured from the flame axis to the
top of the flue reduced by:
– 0.50 m for each change of
direction of the connection
union between boiler and
flue;
– 1.00 m for each metre of
union itself.
Our boilers do not need any particu-
lar connections other than the one
KEY
1
Stainless steel coaxial flue L. 886 code 8096220
2a Stainless steel extension L. 1000 code 8096121
2b Stainless steel extension L. 500 code 8096120
3a 90° stainless steel curve MF code 8095820
3b 45° stainless steel curve MF code 8095920
4
Stainless steel vertical condensation
recovery L. 135 code 8092820
5
Tile with hinge code 8091300
6
Roof outlet terminal L. 1063 code 8091203
7
Kit code 8098812
1
2
3
ø 80/125
to the flue as described above.
2.4.2
Smoke exhaust with
ø 80/125 coaxial flue
(fig. 5)
Our boilers are set to be connected
to ø 80/125 stainless steel coaxial
flues that can be adjusted to the
most suitable direction for room
requirements (fig. 5).
The maximum acceptable length
of the flue must not be over 7.0
equivalent meters.
3
7
TABLE A
90° stainless steel curve MF
45° stainless steel curve MF
Stainless steel extension L. 1000
Stainless steel extension L. 500
Roof outlet terminal L. 1063
Stainless steel coaxial flue L. 886
Stainless steel vertical condensation recovery L. 135
Load losses in meters for each
single accessory to be used in the
exhaust configuration are indica-
ted in Table A.
Only use original SIME accessories
and make sure that connections are
correct as indicated in the instruc-
tions supplied with the accessories.
2.5
ELECTRICAL
CONNECTION (fig. 5/a)
The boiler is fitted with an electricity
6
5
WARNING:
The maximum acceptable
length of the flue must not be
over 7.0 equivalent meters.
Always use the condensation
2
recovery (4) in outlets with
vertical exhaust.
4
7
3
Load loss (mt)
1,80
0,90
1,00
0,50
1,00
0,70
0,70
Fig. 5
47