LCD Panel & Button operation
Detail function/setting and LCD icon indicators. Please see user manual.
Warning indicator
Warning
Overload
Low Battery
Battery is not
connected
Over Charge
Over temperature
Charger failure
Battery fault
Out of bypass
voltage range
Bypass frequency
unstable
EEPROM error
Faults Reference Code
Fault event
Fault
Icon
code
Bus start fail
01
X
Bus over
02
X
Bus under
03
X
Bus unbalance
04
X
Inverter soft
11
X
start fail
Inverter
12
X
voltage high
Inverter
13
X
voltage Low
Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery
service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please contact
your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to
your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered
and upright in a cool, dry location. During storage, recharge the battery
in accordance with the following table:
FSP Manual Guide
Icon (flashing)
Alarm
Sounding twice
every second
Sounding
every second
Fault event
Fault
code
Inverter output
14
short
Battery voltage
27
too high
Battery voltage
28
too low
Over
41
temperature
Overload
43
Charger failure
45
Storage Temperature
-25°C - 40°C
40°C - 45°C
Specifications
Champ Tower 1~3K
MODEL
CAPACITY*
INPUT
Voltage
Voltage Range
Frequency
OUTPUT
Voltage
Regulation
Frequency
Eff.(AC Mode)
Eff.(Bat mode)
Battery
Type/ Numbers
Charge Time
Capacity
Charge Vol.
PHYSICAL&ENVIRONMENT
Humidity
Noise Level
DxWxH (mm)
Net weight(kg)
MANAGEMENT
RS-232 / USB
Optional SNMP
*Long-run model power factor: 0.8
**Product specifications are subject to change without further notice
Champ Rack 1~3K
MODEL
CAPACITY*
Icon
INPUT
Voltage
Voltage Range
Frequency
OUTPUT
Voltage
X
Regulation
Frequency
Eff.(AC Mode)
X
Eff.(Bat mode)
Battery
Type/ Numbers
Charge Time
Capacity
Charge Vol.
PHYSICAL&ENVIRONMENT
Humidity
Noise Level
DxWxH (mm)
Net weight(kg)
MANAGEMENT
RS-232 / USB
Optional SNMP
*Long-run model power factor: 0.8
**Product specifications are subject to change without further notice
Online UPS 1K/2K/3K
Recharge Frequency
Every 3 months
Every 3 months
1K(L)*
2K(L)*
1000VA/900W
2000VA/1800W
208 / 220 / 230 / 240Vac
120-300Vac (Based on load at 50%)
160-280Vac (Based on load at 100%)
40~70Hz
208 / 220 / 230 / 240Vac
± 1%
47~53Hz or 57~63Hz (Synchronized Range)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz (Batt. Mode)
88%
88%
83%
87%
12V/9Ah *2
12V/9Ah *4
4 hours recover to 90% capacity
1.0A for Standard model
1A / 2A / 4A / 6A (Adjustable) for long-run model
27.4Vdc± 1%
54.7Vdc ±1%
20-90% RH @ 0-40°C (non-condensing)
Less than 50dBA @ 1 Meter
282x145x220
379x145x220
*282x145x220
*379x145x220
9.8/*4.1
17/*6.8
Supports Windows, Linux and MAC system
management from SNMP manager/web browser
1K(L)*
2K(L)*
1000VA/900W
2000VA/1800W
208 / 220 / 230 / 240Vac
120-300Vac (Based on load at 50%)
160-280Vac (Based on load at 100%)
40~70Hz
208 / 220 / 230 / 240Vac
± 1%
47~53Hz or 57~63Hz (Synchronized Range)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz (Batt. Mode)
88%
89%
83%
87%
12V/9Ah *2
12V/9Ah *4
4 hours recover to 90% capacity
1.0A for Standard model
1A / 2A / 4A / 6A (Adjustable) for long-run model
27.4Vdc± 1%
54.7Vdc ±1%
20-90% RH @ 0-40°C (non-condensing)
Less than 50dBA @ 1 Meter
310x438x88
410x438x88
*310x438x88
*410x438x88
12/*9
19/*12
Supports Windows, Linux and MAC system
management from SNMP manager/web browser
Charging Duration
1-2 hours
1-2 hours
3K(L)*
3000VA/2700W
90%
88%
12V/9Ah *6
82.1Vdc ±1%
421x190x318
*397x145x220
27.6/*7.4
3K(L)*
3000VA/2700W
90%
88%
12V/9Ah *6
82.1Vdc ±1%
630x438x88
*410x438x88
29.3/*14.2