4. Installation of tanks

Ensure proper stability when installing the
tank. The container must stand evenly and
vertically. The installation surface must be
level and not have any edges or protrusions.
It must be cleaned thoroughly before install-
ing the container. The containers must be
placed at a distance from walls, other compo-
nents and each other such that the fill level,
leaks and status can be visually ascertained
at all times.
4.1 Installation outdoors
CUBE-Tanks are approved for installation out-
doors. When installing outdoors, containers
are to be installed so as to avoid the produc-
tion of any impermissible wind loads and to
reduce the impact of other weather-related
effects to a minimum. If the containers are to
be exposed to a significant wind load, they
must be anchored using suitable wind load
protection, e.g. by connecting the horizontal
pipe straps to ground anchors inserted into
the installation surface. The area used for
outdoor installation should additionally have a
road-quality construction and be watertight.

5. Filling and emptying systems

The filling and emptying line is pre-
installed on the CUBE-Tanks in the factory.
Corresponding installation and operating
instructions are enclosed with the accessory
components, such as counter, fuel filter or
hose reel.
All screwed connections must be checked to
ensure they are leak free!
5.1 Ventilation line
CUBE-Tanks intended for installation
outdoors have a ventilation valve (2")
pre-installed in the factory.
For CUBE-Tanks with a container volume
of 1500 l or 2500 l, which will be installed
inside buildings, the ventilation valve on the
tank must be removed and the ventilation line
laid to the open air on site. Please also see
section 4.3.2 of National Technical Approval
Z-40.21-510 in this regard.
5.2 Overfill protection mechanism
(limiting value transmitter)
for heating oil and diesel fuel
For the versions intended for the storage of
heating oil and diesel fuel, the overfill protec-
tion mechanisms (limiting value transmitters)
are pre-installed in the factory and the
specified installation depths set.

6. Operation

6.1 Operation in heating systems and
diesel filling stations
6.1.1 Filling
Reference is made to section 5.3 of National
Technical Approval No. Z-40.21-510 for pre-
commissioning tests.
The entire system is to be checked for leaks
during initial filling.
The CUBE-Tanks with a container volume of
1500 l and 2500 l may only be filled with per-
manent connections and the use of a suitable
overfill protection mechanism (limiting value
transmitter). CUBE-Tanks with a container
volume of 1000 l may also be filled with an
automatically closing delivery valve and fill
rates of up to 200 l/min in free flow.
6.1.2 Delivery
Delivery is by means of pump, delivery hose
and delivery valve. Please ensure sufficient
ventilation. Please also comply with the
installation and operating instructions of the
accessory components.
6.2 Operation with the other approved media
of the National Technical Approval
Section 5.1.4 of National Technical Approval
Z-40.21-510 as well as the operating instruc-
tions of the accessory components and the
regulations of the water law and for flamma-
ble liquids are to be complied with!
6.3 Maintenance and cleaning
of the CUBE-Tanks
The CUBE-Tanks do not require any special
maintenance. Anti-corrosion agents are not
required.
The good properties of the CUBE-Tanks
result in only slight condensation of water.
Oil sludge must be suctioned out through the
inspection opening using a probe before the
suction hose is reached.