Lp Vapor Pipe Sizing; Installing And Connecting Gas Lines; Shutoff Valve; Flexible Fuel Line - Generac 0060550 Manual De Instrucciones

Ocultar thumbs Ver también para 0060550:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

LP Vapor Pipe Sizing

To determine correct LP Vapor pipe size, find the kW
rating of the generator in the left column, and trace to the
right. The number to the right is the maximum length
(measured in meters/feet) allowed for the pipe sizes on
top. The pipe sizes are measured by inside diameter (ID)
to include any fittings, valves (must be full flow), elbows,
tees or angles. Add 2.5 feet (0.76 m) per any bend, tee or
angle in the pipe to the overall distance.
Table 5.2: LP Vapor Pipe Sizing
Pipe Size (in / mm)
20 kW Synergy
Installing and Connecting Gas
Lines
Both natural gas and LP Vapor are highly volatile
substances, so strict adherence to all safety procedures,
codes, standards and regulations is essential.
Gas line connections should be made by a certified
plumber familiar with local codes. Always use AGA-
approved gas pipe and a quality pipe sealant or joint
compound.
Verify the capacity of the natural gas meter or the LP tank
in regards to providing sufficient fuel for both the
generator and other operating appliances.

Shutoff Valve

See A in
Figure 5-3.
Most applications will require an
external manual full flow shut-off valve on the fuel line.
The valve must be easily accessible.
NOTE: Local codes determine the proper location.
Figure 5-2. Accessory Valve with Manometer Port
Owner's Manual for 60 Hz Synergy Generator™
NOTE: Pipe sizes are using a second stage regulator.
NOTE: The minimum LP tank size is 250 gallons (946 L),
unless unit calculations dictate use of a larger tank.
Vertical tanks, which are measured in pounds (or
kilograms), will not usually meet the minimum tank size
requirement. A 1050 lb (476 kg) vertical tank size
minimum is required.
For 10–12 inches of water column (19–22 mm mercury)
Allowable Pipe Distances (feet / meters)
0.75 / 19
15 / 4.57
NOTE:
manometer port for making fuel pressure checks. This
accessory valve permits making pressure checks without
going into the generator enclosure.
Valves available through Generac and Independent
Authorized Service Dealers:

Flexible Fuel Line

See B in
generator, use a hose assembly that meets the
requirements of ANSI Z21.75/ CSA 6.27 - Connectors for
outdoor Gas Appliances and Manufactured Homes or
AGA-approved flexible fuel line in accordance with local
regulations.
The purpose of flexible fuel line is to isolate vibration from
the generator to reduce possibility of a gas leak at one of
the connection points. It is important the line be installed
with as few bends as possible. The flex fuel line should
be horizontal and plumbed parallel to the back of the
generator.
000743
Fuel Conversion/Gas Connections
1 / 25
115 / 35.05
Figure 5-2
illustrates a fuel shut-off valve with a
1/2 in. ball valve, part number 0K8752
3/4 in. ball valve, part number 0K8754
Figure
5-3. When connecting the gas line to the
CAUTION
Equipment damage. Do not bend flexible fuel line.
Bends in fuel line restrict fuel flow and reduce
ability to absorb vibration.
1.25 / 32
480 / 146.3
(000205)
19

Publicidad

Tabla de contenido
loading

Tabla de contenido