Greenlee CMPL-100 Manual De Instrucciones página 16

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

All manuals and user guides at all-guides.com
Typical Measurements (cont'd)
Three-Phase Three-Wire Measurements:
True Power, Power Factor and Apparent Power Measurement
Notes:
• The + sign on the jaw must face the power source.
• COM connection (black lead) should remain connected to the same phase during both
measurements.
• A positive (+) PF indicates an inductive load. A negative (–) PF indicates a capacitive load.
Power factor value is correct for balanced loads only.
• Both power measurements may be positive, or one may be negative. Make sure all
connections are correct to obtain proper measurements.
Three-Phase Three-Wire Balanced Loads
W
= W
+ W
3Ø3W
RS
TS
KVA
=
3 (KVA
3Ø3W
RS
KVAR
=
[KVA
3Ø3W
3Ø3W
PF
= KW
3Ø3W
3Ø3W
KVA
3Ø3W
16
)
2
2
]
– [KW
]
3Ø3W

Publicidad

Tabla de contenido
loading

Tabla de contenido