For MIX C.S.I. only:
Note
Fault in domestic hot water circuit sensor - 60: the boiler
works regularly but does not ensure the stability of the hot
water temperature which, however, is delivered at a tem-
perature of approximately 50°C.
The fault code is only displayed in standby.
Fig. 36
Fig. 37
12
PROGRAMMING PARAMETERS
.
This boiler incorporates a new generation of electronic
boards that, by setting/modifying operating parameters,
allow the boiler to be personalised to satisfy various system
and/or user requirements.
The programmable parameters are shown in the table on
the next page.
The parameters must be programmed with the boiler
in the OFF position. To do this, press the
until the display shows - - (fig. 38).
During parameter modification operations, the "select
functions" button acts as an ENTER (confirm) button,
the
button acts as an ESC (escape) button.
If no confirmation is given within 10 seconds, the
value is discarded and returns to the previously set
one.
Setting the password
Press and hold down the select functions button and the
button together for about 10 seconds. The display will look
like fig. 39. Enter the password for accessing the parameter
modifications function by turning the domestic hot water
temperature selector to obtain the required value. The
password for accessing the parameter programming
function is located on the back side of the control panel.
Confirm by pressing ENTER.
Modifying parameters
Turn the domestic hot water temperature selector (fig. 40)
to sequentially scroll the two-figure codes of the parameters
indicated in the table.
After identifying the parameter you wish to modify, proceed
as follows:
- press ENTER to access the parameter modification
function.
and
symbols (fig. 37)
CASE B
temporary fault
permanent fault
Fig. 35
Fig. 38
button
Fig. 39
Fig. 40
22
ENTER
ESCAPE