B.1 When unit detect voltage is 230VAC between H and N, unit turn on.
B.2 When unit detect voltage is 0VAC between H and N, unit turn off.
When ROOM THERMOSTAT is set to YES, the indoor temperature sensor Ta can't be set to valid, unit running only
according to T1.
Method C
Hydraulic module is connected with two external temperature controllers, while user interface FOR SERVICEMAN set DUAL
ROOM THERMOSTAT to YES:
C.1 When unit detect voltage is 230VAC between H and N ,the MAIN side turn on.When unit detect voltage is 0VAC between
H and N, the MAIN side turn off.
C.2 When unit detect voltage is 230VAC between C and N, the ROOM side turn on according to climate temp curve. When unit
detect voltage is 0V between C and N, the ROOM side turn off.
C.3 When H-N and C-N are detected as 0VAC, unit turn off.
C.4 when H-N and C-N are detected as 230VAC, both MAIN and ROOM side turn on.
The wiring of the thermostat should correspond to the settings of the user interface. Refer to 10.7 Field setting/Room
Thermostat.
Power supply of machine and room thermostat must be connected to the same Neutral Line and (L2) Phase Line(for
3-phase unit only).
Procedure
Connect the cable to the appropriate terminals as shown in the picture.
Fix the cable with cable ties to the cable tie mountings to ensure stress relief.
3) For 3-way value SV3
5
16
7
6
1ON
N
2ON
1OFF
SV1
Wiring of the 3-way valve is different for NC(normal close) and NO (normal open). Before wiring, read the Installation
& Owner's manual for the 3-way valve carefully and install the valve as showed in the picture. Make sure to connect it
to the correct terminal numbers.
Procedure
Connect the cable to the appropriate terminals as shown in the picture.
Fix the cable reliably.
4) For different functions pumps:
21
9
P_c
N
PUMP_c
CONTROL SIGNAL
OUTPUT
(For zone 2 pump)
NOTE
NOTE
19
18
17
20
8
3ON
N
3OFF
2OFF
SV3
SV2
10
22
P_o
N
PUMP_o
CONTROL SIGNAL
CONTROL SIGNAL
OUTPUT
(For zone 1 pump or
(For solar pump)
outside circulating pump )
N
Voltage
Maximum running current(A)
2
Wiring size(mm
)
Control port signal type
NOTE
11
23
12
P_s
N
P_d
PUMP_s
PUMP_d
CONTROL SIGNAL
OUTPUT
OUTPUT
(For DHW tank
circulating pump)
38
220-240VAC
0.2
0.75
Type 1
24
N