Code
F29
Analog ouptut (FMA)
F30
F31
F34
Analog output (FMI)
F35
F37
Load selection/auto torque boost/auto energy saving
operation
F43
Current limiter
F44
Name
Mode selection
0: Output in voltage (0 to 10V DC)
1: Ouput in current (4 to 20mA DC)
Output adjust.
0 to 200 %
Function
Select a function to be monitored from the followings.
0: Output frequency
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback value (PV)
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration analog output (+10V DC / 20 mA DC)
15: PID process command (SV)
16: PID process output (MV)
Duty
0 to 200 %: Voltage output adjustment
Function
Select a function to be monitored from the followings.
0: Output frequency
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback value (PV)
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration analog output (+)
15: PID process command (SV)
16: PID process output (MV)
0: Variable torque load increasing in proportion to square of
speed
1: Variable torque load increasing in proportion to square of
speed (Higher startup torque required)
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load increasing in proportion to square of
speed)
4: Auto-energy saving operation (Variable torque load increasing
in proportion to square of speed (Higher startup torque
required))
Note: Apply this setting to a load with short acceleration time.
5: Auto-energy saving operation (Auto-torque boost)
Note: Apply this setting to a load with long acceleration time.
Mode selection
0: Disable (No current limiter works)
1: Enable at constant speed (Disabled during acceleration and
deceleration)
2: Enable during acceleration and at constant speed
Level
20 to 120 % (The data is interpreted as the rated output current
of the inverter for 100%)
The shaded function codes are applicable to the quick setup menu
Chapter 6: Function codes and application example
Setting range
Default setting
0
100 %
0
100 %
0
1
0
110 %
13