Fuji Electric FRENIC-Eco FRN-F1 Serie Guía Rápida página 21

Variador de frecuencia para control de bombas y ventilación
Ocultar thumbs Ver también para FRENIC-Eco FRN-F1 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Code
H42
Capacitance of DC link bus capacitor
H43
Cumulative run time of cooling fan
H47
Initial capacitance of DC link bus capacitor
H48
Cumulative run time of capacitors on the printed circuit board
H49
Select starting characteristics (Auto search time for indling
motor's speed)
H50
Non-linear V/f pattern
H51
H56
Deceleration time for forced stop
H63
Low limi ter
H64
H69
Automatic deceleration
H70
Overload prevention control
H71
Deceleration characteristics
H80
Gain for supression of output current fluctuation for motor
H86
Reserved *1
H87
Reserved *1
H88
Reserved *1
H89
Reserved *1
H90
Reserved *1
H91
Reserved *1
H92
Continue to run
H93
H94
Cumulative run time of motor
H95
DC braking (braking response mode)
H96
STOP key priority/start check function
H97
Clear alarm data
H98
Protection/maintenance function
*1
The H86 through H91 are displayed, but they are reserved for particular manufacturers. Unless otherwise specified, do
not access these function codes.
Name
Indication for replacing DC link bus capacitor (0000 to FFFF:
Hexadecimal)
Indication of cumulative run time of cooling fan for replacement
Indication for replacing DC link bus capacitor (0000 to FFFF:
Hexadecimal)
Indication for replacing capacitors on the printed circuit board (0000
to FFFF: Hexadecimal). Resettable
0.0 to 10.0 seconds
Frequency
0.0: Cancel
0.1 to 120.0 Hz
Voltage
0 to 240V: Output a voltage AVR-controlled (for 200V AC series)
0 to 500V: Output a voltage AVR-controlled (for 400V AC series)
0.00 to 3600 seconds
Mode selection
0: Limit by F16 (Frequency Limiter: Low) and continue to run
1: IF the output frequency lowers less than the one limited by F16
(Frequency limiter: Low), decelerates to stop the motor
Lower limiting frequency
0.0 (Depends on F16 (Frequency limiter: Low)
0.1 to 60.0 Hz
0: Disable
3: Enable (Control DC link bus voltage at a constant)
0.00: Follow deceleration time specified by F08
0.01 to 100.00 Hz/s
999: Disable
0: Disable
1: Enable
0.00 to 0.40
0 to 2
25.0 to 120.0 Hz
0 to 3,999
0, 1
0, 1
0, 1
P component: gain
0.000 to 10.000 times
999
I component: time
0.010 to 10.000 seconds
999
Change or reset the cumulative data
0: Slow
1: Quick
STOP key priority
0: Disable
1: Enable
2: Disable
3: Enable
Setting H97 data to "1" clears alarm data and then returns to zero
0 to 63: Display data on the keypad's LED monitor in decimal format
(In each bit, "0" for disabled, "1" for enabled)
Bit 0: Lower the carrier frequency automatically
Bit 1: Detect input phase loss
Bit 2: Detect output phase loss
Bit 3: Select life judgement criteria of DC link bus capacitor
Bit 4: Judge the life of DC link bus capacitor
Bit 5: Detect DC fan lock
Chapter 6: Function codes and application example
Data setting range
Start check function
Disable
Disable
Enable
Enable
Default setting
Set at factory shipping
0.0 seconds
5.0 Hz
0.0 Hz (22kW
(30kW or
or below)
above)
0 (22kW or below)
20 (30kW or above (200V))
40 (30kW or above (400V))
20.0 seconds
0
2.0 Hz
0
999
0
0.10 for 45 kW or avove
(200V series) and for 55 kW
or above (400V series)
0.20 for 37 kW or below
(200V series) and for 45 kW
or below (400V series)
2 for 45 kW or avove (200V
series) and for 55 kW or
above (400V series)
0 for 37 kW or below (200V
series) and for 45 kW or
below (400V series)
25.0 Hz
0
0
0
0
999
999
-
1
0
0
19 (decimal)
(Bits 4,1,0 = 1
bits 5,3,2, = 0)
18

Publicidad

Tabla de contenido
loading

Tabla de contenido