Code
Name
E20
Command assignment to:
[Y1]
E21
[Y2]
E22
[Y3]
E24
[Y5A/C]
E27
[30A/B/C]
E31
Frequency
Detection level
detection (FDT)
E34
Overload early
Level
warning/Current
E35
detection
Timer
E40
PID display coefficient A
E41
PID display coefficient B
E43
LED monitor
Item selection
E45
LCD monitor
Item selection
(only with multi-
functional keypad
E46
Language
TP-G1)
selection
E47
Contrast
control
E48
LED monitor
Speed item
E50
Coefficient for speed indication
E51
Display coefficient for input
watt-hour data
E52
Keypad (menu display mode)
E61
Analog input for
[12]
(Extension
E62
[C1]
function selection)
E63
[V2]
E64
Saving digital reference frequency
E65
Command loss
Level
detection
E80
Detect low torque
Detection level
E81
Timer
E98
Command assignment to:
[FWD]
E99
[REV]
Data setting range
(continuing)
62 (1062): Sequenced start motor 2, inverter-driven
63 (1063): Sequenced start motor 2, commercial-power driven
64 (1064): Sequenced start motor 3, inverter-driven
65 (1065): Sequenced start motor 3, commercial-power driven
67 (1067): Sequenced start motor 4, commercial-power driven
68 (1068): Periodic switching early warning
69 (1069): Pump control limit signal
99 (1099): Alarm output (for any alarm)
0.0 to 120.0 Hz
0: Disable
Current value of 1% to 150% of the inverter rated current
0.01 to 600.00 seconds
-999 to 0.00 to 999
-999 to 0.00 to 999
0: Speed monitor (Select by E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID process command (Final)
12: PID feedback value
14: PID output
15: Load factor
16: Motor output
17: Analog input
0: Running status, rotational direction and operation guide
1: Bar charts for output frequency, current and calculated torque
0: Japanese
1: English
2: Germany
3: French
4: Spanish
5: Italian
0 (Low) to 10 (High)
0: Output frequency
3: Motor speed in r/min
4: Load shaft in r/min
7: Display speed in %
0.01 to 200.00
0.000: (Cancel / reset)
0.001 to 9999
0: Function code data editing mode (Menus #0, #1 and #7)
1: Function code data check mode (Menus #2 and #7)
2: Full-menu mode (Menus #0 through #7)
Selecting function code data assigns the corresponding function to terminals [12], [C1] and [V2]
as listed below
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
5: PID feedback value
20: Analog input monitor
0: Auto saving (at the time of main power turned off)
1: Saving by pressing FUNC/DATA key
0: Decelerate to stop
20 to 120 %
999: Disable
0 to 150 %
0.01 to 600.00 seconds
Selecting function code data assigns the corresponding function to terminals [FWD] and [REV]
as listed below. Setting the value of 1000s in parentheses () shown below assigns a negative
logic input to a terminal.
0 (1000): Select multistep frequency
1 (1001): Select multistep frequency
2 (1002): Select multistep frequency
6 (1006): Enable 3 -wire operation
7 (1007): Coast to stop
8 (1008): Reset alarm
9 (1009): Enable external alarm trip
11 (1011): Switch frequency command 2/1
13: Enable DC brake
15: Switch to commercial power (50 Hz)
16: Switch to commercial power (60 Hz)
17 (1017): UP (Increase output frequency)
18 (1018): DOWN (Decrease output frequency)
Chapter 6: Function codes and application example
Default setting
(M2_I)
(M2_L)
(M3_I)
(M3_L)
(M4_L)
(MCHG)
(MLIM)
(ALM)
50 Hz
100% of the motor
rated current
10.00 seconds
100
0.00
0
0
1
5
0
30.00
0.010
0
0
0
0
0
999
20 %
20.00 seconds
98
99
(SS1)
(SS2)
(SS4)
(HLD)
(BX)
(RST)
(THR)
(Hz2/Hz1)
(DCBRK)
(SW50)
(SW60)
(UP)
(DOWN)
15