6. FUNCTION CODES AND APPLICATION EXAMPLE
6.1 Function codes tables and basic description
Function codes enable the FRENIC-Eco series of inverters to be set up to match your system requirements.
The function codes are classified into eight groups: Fundamental Functions (F codes), Extension Terminal Functions (E
codes), Control Functions of Frequency (C codes), Motor Parameters (P codes), High Performance Functions (H codes),
Application Functions (J codes), Link Function (y codes) and Option Functions (o codes). For Option function (o codes), refer
to the instruction manual for the option.
For further information about the FRENIC-Eco function codes please refer to FRENIC-Eco user's manual.
For further information about pump control please refer to the pump control instruction manual.
F codes: Fundamental functions
Code
F00
Data protection
F01
Frequency command 1
F02
RUN command
F03
Maximum frequency
F04
Base frequency
F05
Rated voltage at base frequency
F07
Acceleration time 1
F08
Deceleration time 1
F09
Torque boost
F10
Electronic thermal overload protection
for motor
F11
F12
F14
Restart mode after momentary power failure
(Mode selection)
F15
Frequency limiter
F16
F18
Bias (frequency command 1)
F20
DC braking
F21
F22
F23
Starting frequency
F25
Stop frequency
F26
Motor sound
F27
Name
0: Disable data protection (function code can be edited)
1: Enable data protection
0: Enable arrow keys on the keypad
1: Enable voltage input to terminal [12] (0 to 10V DC)
2: Enable current input to terminal [C1] (4 to 20 mA)
3: The sum of voltage and current inputs terminals [12] and [C1]
5: Enable voltage input to terminal [V2] (0 to 10V DC)
7: Enable terminal command (UP) / (DOWN) control
0: Enable RUN / STOP keys on the keypad
(Motor rotational direction from digital terminals FWD/REV)
1: Enable terminal command FWD or REV
2: Enable RUN / STOP keys on keypad (forward)
3: Enable RUN / STOP keys on keypad (reverse)
25.0 to 120.0 Hz
25.0 to 120.0 Hz
0: Output a voltage in proportion to input voltage
80 to 240V: Output a voltage AVR -controlled (200V AC series)
160 to 500V: Output a voltage AVR -controlled (400V AC series)
0.00 to 3600 seconds (Entering 0.00 cancels the acceleration
time, requiring external soft -start)
0.00 to 3600 seconds (Entering 0.00 cancels the deceleration
time, requiring external soft -start)
0.0 to 20.0 % (percentatge of the rated voltage at base
frequency (F05)). This setting is effective when F37 = 0,1,3 or 4
Selection
1: For general-purpose motors with built-in-self -cooling fan
motor charact.
2: For inverter-driven motors or high -speed motors with forced -
ventilation fan
Overload
0.0: Disable
detection level
1 to 135% of the rated current (allowable continuous drive
current) of the motor
Thermal time
0.5 to 75 minutes
constant
0: Disable restart (trip immediately)
1: Disable restart (trip after a recovery from power failure)
3: Enable restart (continue to run, for heavy inertia or general
loads)
4: Enable restart (restart at the frequency at which the power
failure ocurred, for general loads)
5: Enable restart (restart at the starting frequency, for low -inertia
load)
High
0 to 120.0 Hz
Low
0 to 120.0 Hz
-100.00 to 100.00 %
Start freq.
0.0 to 60.0 Hz
Braking level
0 to 60 % (Rated output current of the inverter interpreted as
100%)
Braking time
0.00: Disable
0.01 a 30.0 seconds
0.1 to 60.0 Hz
0.1 to 60.0 Hz
Carrier
0.75 to 15 kHz (22kW or below)
frequency
0.75 to 10 kHz (30kW to 75kW)
0.75 to 6 kHz (90kW or above)
Sound tone
0: Level 0 (Inactive)
1: Level 1
2: Level 2
3: Level 3
Chapter 6: Function codes and application example
Setting range
Default setting
0
0
2
50.0 Hz
50.0 Hz
400 V
20.0 seconds
20.0 seconds
Depend on the inverter power
capacity
1
100 % of the motor rated current
5.0 minutes
10.0 minutes
(22kW or
(30kW or
below)
above)
0
70.0 Hz
0.0 Hz
0.00 %
0.0 Hz
0 %
0.00 seconds
0.5 Hz
0.2 Hz
2 kHz
0
12