Code
Name
E98
Command assignment to:
[FWD]
E99
[REV]
C codes: Control functions of frequency
Code
C01
Jump frequency
C02
C03
C04
C05
Multistep frequency
C06
C07
C08
C09
C10
C11
C30
Frequency command 2
C32
Analog input adjustment for
C33
[12]
C34
C37
Analog input adjustment for
C38
[C1]
C39
C42
Analog input adjustment for
[V2]
C43
C44
C50
Bias reference point (Frequency command 1)
C51
Bias for PID command
C52
C53
Selection of normal/inverse operation
(Frequency command 1)
(continuing)
19 (1019): Enable write from keypad (Data changeable)
20 (1020): Cancel PID control
21 (1021): Sw itch normal/inverse operation
22 (1022): Interlock
24 (1024): Enable communications link via RS485 or field bus (option)
25 (1025): Universal DI
26 (1026): Select starting characteristics
30 (1030): Force to stop
33 (1033): Reset PID integral and differential components
34 (1034): Hold PID integral component
35 (1035): Select local (keypad) operation
38 (1038): Enable to run
39: Protect motor from dew condensation
40: Enable integrated sequence to switch to commercial power (50 Hz)
41: Enable integrated seq uence to switch to commercial power (60 Hz)
50 (1050): Clear periodic switching time
51 (1051): Enable pump drive (motor 1)
52 (1052): Enable pump drive (motor 2)
53 (1053): Enable pump drive (motor 3)
54 (1054): Enable pump drive (motor 4)
87 (1087): Switch run command 2/1
88: RUN forward 2
89: RUN reverse 2
98: RUN forward
99: RUN reverse
The shaded function codes are applicable to the quick setup menu
Name
1
0.0 to 120.0 Hz
2
3
Band
0.0 to 30.0 Hz
1
0.00 to 120.00 Hz
2
3
4
5
6
7
0: Enable arrow keys on the keypa d
1: Enable voltage input to terminal [12] (0 to 10V DC)
2: Enable current input to terminal [C1] (4 to 20 mA)
3: The sum of voltage and current inputs terminals [12] and [C1]
5: Enable voltage input to terminal [V2] (0 to 10V DC)
7: Enable terminal com mand (UP) / (DOWN) control
Gain for terminal input [12]
0.00 to 200.00 %
Filter time constant
0.00 to 5.00 seconds
Gain refrence point
0.00 to 100.00 %
Gain for terminal input [C1]
0.00 to 200.00 %
Filter time constant
0.00 to 5.00 seconds
Gain reference point
0.00 to 100.00 %
Gain for terminal input [V2]
0.00 to 200.00 %
Filter time constant
0.00 to 5.00 seconds
Gain reference point
0.00 to 100.00 %
0.00 to 100.0 %
Bias value
-100.00 to 100.00 %
Bias reference point
0.00 to 100.00 %
0: Normal operation
1: Inverse operation
Chapter 6: Function codes and application example
Data setting range
Data setting range
Default setting
(WE-KP)
(Hz/PID)
(IVS)
(IL)
(LE)
(U-DI)
(STM)
(STOP)
(PID-RST)
(PID-HLD)
(LOC)
(RE)
(DWP)
(ISW50)
(ISW60)
(MCLR)
(MEN1)
(MEN2)
(MEN3)
(MEN4)
(FR2/FR1)
(FWD2)
(REV2)
(FWD)
(REV)
Default setting
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
2
100.0 %
0.05 seconds
100.0 %
100.0 %
0.05 seconds
100.0 %
100.0 %
0.05 seconds
100.0 %
0.00 %
0.00 %
0.00 %
0
16