ning the pressure-relief valve.
2.5. 1
Emptying the system (fig. 5)
Use the drain tap to empty the system (9).
Turn off the boiler before doing this.
2.6
FLUES/CHIMNEYS
The flue or chimney used to release the
products of combustion into the atmosphe-
re must comply with current legislation.
2.6. 1
Passing flue pipes through
an existing chimney
When renovating or passing flue pipes
through an existing chimney, use only flues
which are declared suitable for the purpo-
se by the manufacturer, following the
instructions for installation and use provi-
ded by the manufacturer.
2.7
INSTALLATION COAXIAL DUCT
(vers. "BF TS")
The air inlet-smoke outlet assembly ø
60/100 is supplied in a kit code 8084811
complete with mounting instructions. With
the curve supplied in the kit the maximum
horizontal length of the flue must not
exceed 3.5 metres in model "25 BF TS" - 3
metres in models "30 - 35 BF TS". The dia-
grams in fig. 6 illustrate a number of exam-
ples of different coaxial outlets.
2.7. 1
Coaxial flue diaphragm
The boiler is supplied as standard with a ø
86 diaphragm (version "25 - 35 BF TS")
and ø 87.5 diaphragm (model "30 BF TS").
With outlet type C12-C42, install diaph-
ragm ø 86 or ø 87.5 only if the coaxial
flue is less than 1 metres long. For C32
discharge options, it is necessary to order
the optional diaphragm separately and use
it in accordance with the instructions provi-
ded in figure 7.
"30 OF S" models
5
8
3 2
9
4
KEY
1 D.H.W. inlet/outlet manifold
2 Fill tap
3 D.H.W. filter
4 By-pass
KEY
1
Coaxial flue kit L. 810
x + y = max 3,5 m "25"
code 8084811
x + y = max 3,0 m "30-35"
2 a Extension L. 1000
code 8096103
2 b Extension L. 500 code 8096102
3
Vertical extension L. 200 code 8086908
4
Additional 90° curve code 8095801
6
Articulated tile code 8091300
7
Roof outlet terminal L. 1284 code 8091200
8
Vertical condensation collector L. 200 cód. 8092803
IMPORTANT:
– Each additional 90° curve installed reduces the available
length by 0.90 metres.
– Each additional 45° curve installed reduces the available
length by 0.45 metres.
– It is advisable to assemble the condensation collector
(8) on vertical segments exceeding 2.5 metres in length
and to limit maximum length to 4 metres.
With outlet type C12-C42, install diaphragm ø 86 or ø 87.5 only if the coaxial flue is
less than 1 metres long.
With outlet type C32, use the following diaphragms, depending on flue length and without
any additional curves:
Installations with vetrical
extension L. 200 code 8086908
Diaphragm
Diaphragm
ø 86
ø 87,5
(cod. 6028623) (cod. 6028624)
L min = 1,3 m
L min = 2,5 m
L max = 2,5 m
L max = 4 m
"25 - 30 - 35 BF TS" models
8
5
1
3
2
5 Water rate adjuster
6 D.H.W. exchanger
7 Microswitches
8 Water flow switch
9 Boiler discharge
x
2
4
y
3
C42
C32
max 3,5 m "25"
max 3,0 m "30-35"
C12
Installations with vertical condensation
collector code 8092803
Without
Diaphragm
diaphragm
ø 87,5
(cod. 6028624)
L min = 4 m
L max = 2,5 m
L max = 5 m
ES
PT
7 6
GB
GR
RO
9
4
RUS
Fig. 5
7
6
2
3
8
1
Fig. 6
None
diaphragm
L min = 2,5 m
L max = 4 m
Fig. 7
75
IT