CONTACT
FC
DESCRIPTION
N.B.
Adjust the door open limit switch so that the overhead door stops after activation of the
limit switch and before the door open stop.
Adjust the door closed limit switch so that it is activated when the door reaches a
distance no greater than 5 cm from the door closed stop.
Once activated, the limit switch must not be released until the manoeuvre is completed.
If the limit switch is adjusted correctly, when the limit switch is activated, the door
continues as far as the stop and then stops.
If the limit switch is not adjusted correctly, the door reverses direction.
WARNING! The pressure exerted against the stop is determined by the parameter
This value must be set in relation to the type of overhead door structure, to prevent
problems such as bending or warping.
FA
N.B.: After each adjustment to the positions of the limit switches, the travel acquisition
FC ≤5 cm
.
49