11 Disposal

Dispose of the AS3-SV safety valve in accordance with the currently applicable
u
regulations in your country.

12 Troubleshooting

Danger of injury by dismantling the valve!
Compressed and loaded springs may suddenly be released when dismantling
the valve.
1. Never dismantle the valve.
2. Do not attempt to perform any unauthorized repairs.
Check the connections, operating voltage, and working pressure of the rele-
u
vant system part if malfunctions occur.
Additional help for malfunctions can be found in the following table:
Malfunction
Possible cause
Pressure/flow level is not
Operating pressure is too low Increase the operating pres-
reached or drops off slowly
Leak on tubing
No output pressure on output
Incorrect control
2 and LED display differs from
the normal display (see be-
low)
RUN LED is off
Device is not supplied with a
voltage
LED IN 1, IN 2 off
The corresponding safety in-
put does not have a signal
The IN 1, IN 2 LEDs flash
Control of signals IN 1 and
quickly
IN 2 outside of the synchro-
nization time
OUT LED flashes slowly
No start signal on X2
ERR LED flashes
An error has occurred in the
device
Additional help for malfunctions can be found in the following table:
ERR error num-
ERR error num-
ber flashes long
ber flashes short
1
1
1
2
2
4
4
3
3
8
3
9
4
1
4
2
AVENTICS™ AS3-SV | R412026750-BAL-001-AE | English
WARNING
Remedy
sure
Check tubing diameter
Check tubing and tubing con-
nections
Troubleshooting using the
LED display
(Normal state: RUN, IN 1, IN 2
and OUT illuminate, ERR is
off)
Supply a voltage to the device
according to the instructions
Check the wiring and control
of safety inputs
Check signal sequence on
IN 1 and IN 2
Check the wiring and control
of the start signal
Establish the fault number us-
ing the flash code and carry
out troubleshooting in accor-
dance with the chapter "Sig-
nal sequence when a fault oc-
curs".
Explanation of errors
Remedy
Supply voltage too low
Increase the power supply.
Use a cable with a larger
diameter
Supply voltage too high
Reduce the power supply
Cross-circuit between in-
Check the wiring and cor-
puts S12 and S22
rect if necessary
Supply voltage is detected
Select a supply voltage ac-
as an AC voltage
cording to the technical
data
Time monitoring during
Check the compressed air
pressurization
supply. Change the soft
start setting.
Time monitoring during
Apply a minimum pressure
exhaust
of 2 bar at port 2 in order
to bring the valve to home
The exhaust process is ini-
position (see "Soft start").
tiated during the filling
process. The exhaust valve
remains in an undefined
position and therefore
does not report its posi-
tion in the exhaust posi-
tion.
Time monitoring during
Silencer blocked, replace
exhaust
silencer
Time monitoring during
Silencer blocked, replace
exhaust
silencer
ERR error num-
ERR error num-
ber flashes long
ber flashes short
3
4
2
9
3
1
3
6
If you are unable to troubleshoot the AS3-SV safety valve malfunction yourself:
Disassemble the AS3-SV safety valve as described in chapter "Disassembly
u
and exchange" and send it to AVENTICS GmbH. You can find the address on
the back of the operating instructions.

13 Spare parts and accessories

Designation
Blocking set for individual mounting
Mounting kit for assembly in a maintenance unit.

14 Technical data

General data
Dimensions (length x width x height)
Weight
Design
Control
Working pressure min./max.
Residual pressure in the worst case
Ambient temperature min./max.
Medium temperature min./max.
Ambient operating conditions
Permissible medium
Max. particle size
Oil content of compressed air
The pressure dew point must be at least 15°C below the ambient and medium temperatures
and must not exceed 3°C.
The oil content of compressed air must remain constant during the life cycle.
Mounting orientation
Mounting
Use only the approved oils from AVENTICS.
u
Electrical data
Voltage
Supply voltage
Inputs S12, S22, X2
Clock output S11, 21
Cable length
Line resistance
Power consumption
Protection class according to IEC 60529/
EN 60529
Electrical connections
Tightening delay
Drop-out delay
Override time in case of voltage drop
Explanation of errors
Remedy
Undefined level on input
Check the signals on plug
X2
XPS and the wiring
Undefined level on input
Check the signals on plug
S12
X2D and the wiring
Undefined level on input
Check the signals on plug
S22
X2D and the wiring
Time monitoring during
Check the pressure supply.
pressurization
Apply a minimum pressure
of 2 bar at port 1.
Mat. no.
R412007367
R412026828
138.7 mm x 63 mm x 305.5 mm
4185 g
Redundant, 3/2 Normally Closed, interne
monitoring, dual valve
Electromagnetically externally piloted with
air-assisted spring return. One magnet per
valve element (2 in total) - both must be op-
erated simultaneously.
2 ... 10 bar
0.2 bar
-5 °C / +50 °C
-5 °C / +50 °C
Max. height above sea level: 2000 m
Compressed air acc. to ISO 8573-1
5 µm
3
0 ... 1 mg/m
Any, preferably vertical
Inline assembly - modular/with thread.
24 V DC +/-10%
Power pack/mains supply
SELV power pack in accordance with
DIN EN 60950 for operation in a PELV circuit
in accordance with EN/IEC 60204-1
24 V DC, 8 mA
20 V DC, 10 mA per output
1500 m at 1.5 mm²
2500 m at 2.5 mm²
max. 40 Ω
280 mA
IP65 (only when assembled and with all plugs
connected)
1x plug and 1x socket, 5-pin, M12
< 150 ms
In case of emergency stop: < 10 ms
In case of power failure: < 10 s
5 msec