Sew Eurodrive MOVIGEAR performance Instrucciones De Funcionamiento página 80

Unidad de accionamiento mecatrónica

Publicidad

Instalación eléctrica
5
Normas de instalación
Branch Circuit Protection
Motor Overload Protection
Surrounding Air Temperature Rating
Wiring Diagrams
80
Instrucciones de funcionamiento – MOVIGEAR
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
SCCR: 65 kA /500 V when protected by
Non-semiconductor fuses
(currents are maximum values)
40 A max./600 V
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150 % of the rated motor current.
The devices are suitable for an ambient temperature of 40 °C, max. 60 °C with de-ra-
ted output current. To determine the output current rating at temperatures above
40 °C, the output current should be de-rated by 3 % per K between 40 °C and 60 °C.
For wiring diagrams, refer to chapter "Electrical Installation".
®
performance
Inverse time circuit breakers
(currents are maximum values)
40 A max./500 V min.