Descargar Imprimir esta página

Collective Fault Signal (Ssm); Connect - Wilo Yonos MAXO Instrucciones De Instalación Y Funcionamiento

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 126
en
1.
Individually connect and secure both motors.
2.
Provide separate switchgear (e.g.,: Wilo-Connect module Yonos MAXO (accessories)).
3.
Make identical settings.
7.4

Collective fault signal (SSM)

The contact of the collective fault signal (potential-free normally closed contact) can be connected to a build-
ing automation system. Internal contact is closed in the following cases:
The pump has zero current.
There is no fault.
The control module has failed.
DANGER
Risk of fatal electrical shock!
Danger to life through voltage transmission, if mains and SSM pipe are led together through a
5-wire cable.
• Do not connect SSM pipe to protective low voltage.
Connection values
Permitted minimum: 12 V DC, 10 mA
Permitted maximum: 250 V AC, 1 A, AC 1
During connection of the SSM pipe to the network potential:
SSM phase = live wire L1
7.5

Connect

DANGER
Risk of fatal electrical shock!
Immediate risk of fatal injury if live components are touched.
• Electrical connection may only be carried out by a qualified electrician and in accordance
with the applicable regulations!
• Before commencing work, switch off the power supply and secure it from being switched
on again.
1.
Prepare the cable as indicated in the Figure (Fig. X).
2.
Unscrew the screw from the plug (Fig. XI).
3.
Remove the plug.
4.
Unscrew cable ducts (Fig. XII).
5.
Flip open the plug.
6.
Remove the elastic fastener from the cable ducts using a small screwdriver (Fig. XIII).
7.
Guide the cable through the cable ducts to the connection sockets.
8.
Connect the wires in the correct position (Fig. XIV).
9.
Close the plug and unscrew cable ducts (Fig. XV).
10. Insert the plug and fasten with screw (Fig. XVI).
11. Restore the power supply.
56
Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08

Publicidad

Solución de problemas

loading

Este manual también es adecuado para:

Yonos maxo-dYonos maxo-z