ATTENTION!
If simultaneous faults occur on two or more IGBTs of CFW900 during the
activation of the safety function, it is possible that CFW900 delivers sufficient
energy to cause a magnetic alignment between the rotor and the internal
magnetic poles of the motor. This movement depends on the number of
poles of the motor and is limited to a maximum of 180°. Although this event is
unlikely to occur, make sure that this possibility cannot cause harm to people
or damages to machinery.
5.2 STATES AND FAULTS RELATED TO STO90
STO - SAFE TORQUE-OFF STATE
Description:
It indicates to the user that the STO state is active.
Possible Causes:
Actuation of the safety inputs (STO1 and STO2).
Safety input circuit not installed.
Safety input circuit de-energized.
SS1-t - SS1 CONTROLLED TIMING
Description:
It indicates to the user that STO90 is executing the timing of the SS1-t safety function, while
CFW900 central control decelerates the motor.
Possible Causes:
Actuation of the safety inputs (STO1 and STO2) with the SS1-t safety function configured.
Fault detected with the SS1-t safety function configured.
CONFIG - STO90 PROGRAMMING MODE
Description:
It indicates to the user that STO90 is in the programming mode of the safety functions.
Possible Causes:
Activation of the DIP switches S2 of STO90 during the STO state.