Installation
Configuration
2.3.2 DIP Switches S2
As shown in
Table 2.6 on page
mode of STO90, enabling the selection of which internal safety function will be used, as well as the
definition of the delay time in case of SS1-t. The programming procedure is described in details
in
Section 4.2 CONFIGURING THE SAFETY FUNCTION on page
16 | CFW900
Table 2.5: DIP switches S1
Both DIP switches set to "D" (dry contact)
This configuration must be chosen when the safety signals are
controlled by dry contacts as shown in
14
One DIP switch set to "D" (dry contact) and the other set to "O" (OSSD)
This is not a valid combination and results in a fault state (F0160)
Both DIP switches set to "O" (OSSD)
This configuration must be chosen when safety signals are controlled
by an OSSD output, as shown in
17, the DIP switches S2 control the access to the programming
Description
Figure 2.2 en la página
Figure 2.3 en la página 15
20.