ELBOW CONDUIT ( eld supply)
SHIELDING PLATE
GROUND
WIRE
LOW
VOLTAGE
WIRE
Voltage Ports
NOTE: The communicating thermostat is able to search and
identify the indoor and outdoor units when power is applied to
the system. Refer to the communicating thermostat's instal-
lation instructions for more information.
Connect low voltage communication wires (1, 2) to low volt-
age pigtail provided.
C
W
ommuniCation
iring
NOTE: A terminal block is attached with the control board to
make wiring connections for the thermostat. Connect the wire
to the terminal block. (1.5 - 3.0 ton only) A removable plug con-
nector is provided with the control board to make thermostat
wire connections. Remove the plug, connect the wires to the
plug, and then replace. (3.5 - 5.0 ton only) It is strongly recom-
mended that you do not connect more than two wires into a
single terminal in the field because there is a risk of the wires
becoming loose, which may result in communication error.
Refer to Troubleshooting Tables for error codes.
To wire the system components, it is strongly recommended
to use the same type and same gauge for the wires prepared
in the field. (For best results, use 18 AWG.) However, commu-
nications reliability may be improved by using a high quality,
Attach hole size Φ22.2 or Φ28.6
CONDUIT PLATE (accessory)
* Attach CONDUIT PLATE in the
direction shown above
HIGH
VOLTAGE
WIRE
Tie high voltage
wire and ground
wire with clamp
material
(accessory)
INSULATION
TUBE
shielded, twisted pair cable for the data transmission lines.
Finally, be sure to confirm that the wires do not come off each
terminal after all connections are finished.
NOTE: When connecting the connection wires to the terminal
block, be sure to curl the end of the lead.
Good
Strip wire end
to this point.
Good
t
-W
o
, F
Wo
ire
utdoor
Typical wiring will consist of two wires between the indoor unit
and outdoor unit, and four wires between the indoor unit and
thermostat. The figure that follows shows the required wires:
data lines, 1 and 2; "R" (24 VAC hot) and "C" (24 VAC common).
Never connect the power wiring to communication terminal.
(1, 2, R, C)
<In case of Air Handler>
Communicating Thermostat
1
2
C R
125 �.(*)
Air Handler BIower
1
2
R C
integrated ControI Module
250 �.(*)
Outdoor Unit
1
2
R C
integrated Control Module
(*) AIIowable Maximum Length
System Wiring
ATTENTION INSTALLER -
IMPORTANT NOTICE!
Please read carefully before installing this unit.
• Low voltage terminal C from indoor unit must connect
to low voltage terminal C on thermostat and low voltage
terminal R from indoor unit must connect to low voltage
terminal R on thermostat. Verify wires are not reversed.
(Note: The order of the terminals of the indoor unit and
your thermostat may be different system wiring.)
• Do not attach any wires to the R & C Terminals on the
Outdoor Unit, as they are not needed for inverter unit.
• Data line terminal #1 from outdoor unit must connect
to terminal #1 on indoor unit and thermostat and data
line terminal #2 from outdoor unit must connect to
terminal #2 on indoor unit and thermostat. Verify wires
are not reversed.
21
ASXS6S̲3P679063-2D̲ALL̲220729.pdf
Wrong
Wrong
-W
i
W
our
ire
ndoor
iring
<In case of Cased Coil>
Communicating Thermostat
1
2
C R
125 �.(*)
Cased Coil
1
2
R C
integrated ControI Module
Gas Furnace or Module BIower
1
2
R C
integrated ControI Module
250 �.(*)
Outdoor Unit
1
2
R C
integrated ControI Module
(*) AIIowable Maximum Length