Descargar Imprimir esta página

Amana ASXS61A Serie Instrucciones De Instalación página 8

Publicidad

Idiomas disponibles

Idiomas disponibles

• Wall facing outlet side is lower than unit
1. Open top installation
L
A
L ≤ 0.5H
10" Minimum
0.5H < L ≤ H
12" Minimum
Double decker installation
1. Wall facing outlet side
Multiple rows of series installation
(There is no restriction on the height of the wall.)
1. One row of stand alone
installation
2. Closed top installation*
2. Wall facing inlet side
2. Rows of series installation*
(2 or more)
8
ASXS6S̲3P679063-2D̲ALL̲220729.pdf
*
,
L
L ≤ 0.5H
L ≤ H
0.5H < L ≤ H
Use a stand to meet L ≤ H or keep
70" or more clearance to front wall.
If using stand, required dimension
L > H
A is same as L ≤ H.
If not using stand, dimention A is
12" minimum.
Note:
• Do not stack more than two units.
• If drain water might freeze, install the roof
between the units.
• To avoid frost under the bottom frame,
leave 20" minimum clearance between
the units.
L
L ≤ 0.5H
L ≤ H
0.5H < L ≤ H
L > H
Note:
• Do not install inlet side and outlet side face
to face.
* Maximum two units are allowed to install.
unit: inch
A
10" Minimum
12" Minimum
A
10" Minimum
12" Minimum
Not available.

Publicidad

loading

Este manual también es adecuado para:

Aszs61a serie