Programmable parameters
DESCRIPTION PARAMETERS
PAR.
1
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
2
THIS PARAMETER IS NOT influential
3
INSULATION LEVEL OF BUILDING
10
DHW MODE
11
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
12
WATER TANK MAXIMUM SET-POINT
13
DELIVERY TERMPERATURE EXT. WATER TANK
14
DELTA EXTERNAL WATER TANK (ON)
20
HEATING MODE
21
HEATING CIRCUIT MAXIMUM SET-POINT
22
MINIMUM HEATING SET POINT
23
MAXIMUM HEATING VENTILATOR SPEED
24
MINIMUM HEATING VENTILATOR SPEED
25
DIFFERENTIAL HEATING POSITIVE
26
DIFFERENTIAL HEATING NEGATIVE
28
MAX HEATING POWER REDUCTION TIMER
29
FORCED HEATING SHUT DOWN TIMER
30
HEATING TIMER RESET FUNCTION
31
MAXIMUM HEATING SET POINT 2CH (II circuit)
32
MINIMUM HEATING SET POINT 2CH (II circuit)
35
DIFFERENTIAL HEATING POSITIVE 2CH
36
DIFFERENTIAL HEATING NEGATIVE 2CH
40
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
41
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
42
S.A.R.A. FUNCTION
43
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
44
THERMOREGULATION FUNCTION
45
INCLINATION THERMOREGULATION CURVE (OTC)
46
THERMOREGULATION FUNCTION 2CH
47
INCLINATION THERMOREGULATION CURVE (OTC)
2CH
48
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
50
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
51
HEAT REQUEST TYPE CH1 (I circuit)
52
HEAT REQUEST TYPE CH2 (II circuit)
61
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
62
HEATING ANTIFREEZE FUNC. DELIVERY TEMP. (ON)
63
WATER TANK ANTIFREEZE FUNC. DELIV. TEMP. (ON)
65
EXTERNAL SENSOR REACTIVITY
85
SEMI-AUTOMATIC FILLING
86
AUTOMATIC FILLING PRESSURE (ON)
87
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
90
VARIABLE SPEED PUMP
92
ENABLE POST-CIRCULATION FROM DHW TO
HEATING
93
DURATION OF POST-CIRCULATION FROM DHW TO
HEATING
94
PUMP IN CONTINUAL MODE CH1 (CIRCUIT 1)
95
PUMP IN CONTINUAL MODE CH2 (CIRCUIT 2)
** The value is expressed on the display in revs/min/100 (example 3.600 = 36)
Some defaults may be different from what is indicated in the table for updates to the board
UNIT OF
MIN
MEASURE
10-16-20-26-30-34-50-70
min
5
0 (OFF)
1 (Instantaneous)
2 (Mini-tank)
3 (External water-tank with thermostat)
4 (External water-tank with sensor)
5 (DS built-in storage tank)
6 (3S built-in storage tank)
° C
40
°C
50
°C
0
0 (OFF)
1 (ON)
2 (not used)
3 (CONNECT AP)
4 (not used)
5 (not used)
6 (CONNECT AT/BT)
7 (Remote panel + CONNECT AT/BT)
8 (Remote panel + zone valves)
° C
40
°C
20
revs/min
revs/min
G20 G31
25kW 12** 19**
35kW 12** 19**
°C
2
°C
2
min
0
min
0
-
0 (NO)
°C
40
°C
20
°C
2
°C
2
0 (OFF)
1 (AUTO)
0 (OFF)
1 (AUTO)
-
2,5
0 (OFF)
1 (AUTO)
-
2,5
-
0
-
0
°C
0
°C
0
0 (very fast)
0 (disabled)
1 (enabled)
bar
0,4
-
0
-
0
-
1
-
0
-
0
DEFAULT
MAX
(setted in
factory)
1
20
20
5
6
60
80
60
85
80
10
5
1
80
80
39
20
G20
G31
MAX
25kW 60**
60**
35kW 60**
59**
MIN
10
6
10
6
20
15
20
5
1 (YES)
0
80
45
39
25
10
3
10
3
1
1
1
1
1
40
20
1
40
10
0
1
1
0
1
0
4
10
6
10
6
255 (very slow)
20
1
1,0
0,6
1
100
41
1
0
255
5
1
0
1
0
ENGLISH
PARAMETERS
(setted by techn.
assist. centre)
19

Publicidad

loading

Este manual también es adecuado para:

Exclusive boiler green he 25 b.s.i.