Power And Grounding Wiring, Circuit Breakers And Fuses - WEG CFW500 Manual Del Usuario

Ocultar thumbs Ver también para CFW500:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Connection

3.2.2 Power and Grounding Wiring, Circuit Breakers and Fuses

ATTENTION!
Use proper cable lugs for the power and grounding connection cables. Refer
to
Table B.1 on page 146
Keep sensitive equipment and wiring at a minimum distance of 0.25 m from the
inverter and from the cables connecting the inverter to the motor.
It is not recommended the use of mini circuit breakers (MDU), because of
the actuation level of the magnet.
ATTENTION!
Residual Current Device (RCD):
When installing an RCD to guard against electrical shock, only devices with
a trip current of 300 mA should be used on the supply side of the inverter.
Depending on the installation (motor cable length, cable type, multimotor
configuration, etc.), the RCD protection may be activated. Contact the RCD
manufacturer for selecting the most appropriate device to be used with
inverters.
NOTE!
The wire gauges listed in
Installation conditions and the maximum permitted voltage drop must be
considered for the proper wiring sizing.
In order to meet UL requirements, use ultra fast (for frame sizes A, B and C),
and use fuse type J or circuit breaker (for frame sizes D and E) fuses at the
inverter supply with a current not higher than the values presented in
B.1 on page
14 | CFW500
for recommended wiring, circuit breakers and fuses.
Table B.1 on page 146
146.
are orientative values.
Table

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cfw500 serieCfw500aCfw500bCfw500cCfw500dCfw500e

Tabla de contenido