Troubleshooting and Maintenance

6 TROUBLESHOOTING AND MAINTENANCE

6.1 FAULT AND ALARMS

NOTE!
Refer to the quick reference and to the programming manual of the CFW500
for further information about each fault or alarm.

6.2 SOLUTIONS FOR THE MOST FREQUENT PROBLEMS

Problem
Point to be Verified
Motor will not
Incorrect wiring
start
Analog reference
(if used)
Wrong settings
Fault
Motor stall
Motor speed
Loose connections
oscillates
Defective speed
reference
potentiometer
Oscillation of the
external analog
reference
Too high or
Incorrect settings
too low motor
(reference limits)
speed
Control signal of the
analog reference
(if used)
Motor nameplate
Display off
HMI connections
Power supply voltage
Main supply fuse open 1. Replace the fuses

6.3 DATA TO CONTACT THE TECHNICAL ASSISTANCE

For information or service request, it is important to have at hand the following data:
Inverter model.
Serial number and manufacturing date of the product identification label (refer to
IDENTIFICATION LABELS on page
34 | CFW500
Table 6.1: Solutions for the most frequent problems
1. Check all the power and command connections
1. Check if the external signal is properly connected.
2. Check the status of the control potentiometer (if used)
1. Check if the parameters values are correct for the
application
1. Check if the inverter is disabled due to a fault condition
1. Decrease the motor overload
2. Increase P0136, P0137 (V/f)
1. Stop the inverter, turn off the power supply and tighten all
the connections
2. Check all the internal connections of the inverter
1. Replace the potentiometer
1. Identify the cause of the oscillation. If the cause is electrical
noise, use shielded cables or separate them from the
power or command wiring
2. Interconnect the GND of the analog reference to the
grounding connection of the inverter
1. Check whether the content of P0133 (minimum speed) and
P0134 (maximum speed) are properly set for the motor and
application used
1. Check the level of the reference control signal
2. Check the setting (gain and offset) of parameters P0232 to
P0240
1. Check whether the motor used matched the application
1. Check the connections of the inverter external HMI
1. Rated values must be within the limits specified below:
200 / 240 V power supply: - Min: 170 V - Max: 264 V
380 / 480 V power supply: - Min: 323 V - Max: 528 V
9).
Corrective Action
Section 2.4