Devices without internal residual current
device must be connected via a separate
residual current device (see also
IEC 60364-7-722 (according to DIN
VDE 0100 722 in Germany).
Devices with integrated residual current
device are supplied with type B.
No other circuits may be connected to this
residual current device.
For the versions Start, Start E, Standard E and Basic E, the
required residual current device (RCD) must be provided
on site.
5.3.3 Laying the supply line
f All necessary lines to the location must be surface-
mounted or concealed.
Î Notes regarding the cables:
"5.5 Installing the device" and "5.6 Electrical connec-
tion"
Surface installation
MENNEKES recommends mounting the device on
an on-site cable duct
(height 30 mm × width 45 mm).
If the cables or cable duct comes from below, you have to
break out the pre-cut opening in the front enclosure part.
Concealed installation
In a concealed installation of wires, their positions must be
arranged in accordance with the drilling jig.
5.4 Opening the device
1
Fig.: 13. Opening the device
When delivered, the front enclosure part (2) is not attached
with screws. The screws (1) are stored in the enclosed
accessory bag.
f Ensure that the power supply is switched off.
f Remove the upper enclosure part (2).
f Remove screws (3) of front panel and fold down front
panel (4).
2
3
3
1
4
15
EN