6.10 Connecting nitrogen bottles
(ASC2000RPA only)
To check for leaks using the nitrogen test, an external nitrogen bottle
needs to be connected to the AirCon Service Center.
The pressure at the nitrogen bottle's output must not exceed 12 bar.
1. Set the pressure regulator on the nitrogen bottle to max. 12 bar.
2. Hook up the connection hose to the nitrogen bottle and the
connection (8) for the nitrogen bottle.
3. Open the nitrogen bottle's valve.
AirConServiceCenter
First start-up
8
75