Loosen the swivel nut, pull out the rubber stopper
3
out of the AC connector.
5
Pull out the terminal block inside.
7
9
Pull up the latch.
The second step is subject to the actual situation.
1. When the outer diameter of cables is 17.5~18.5 mm,
cut the membrane in two holes before cable threading.
2. When the the outer diameter of cables is 19~21 mm,
cut the membrane first, pull out the rubber tubing inside
4
and cut off the tubing before cable threading.
Plug L1/ L2/ L3/ N/ PE cables into the
6
corresponding ports of the terminal block.
Screw to tighten
Grid and EPS
cables with an
Allen key.
Allen key
Insert the terminal block and rubber stopper back
2.5±0.1 N·m
8
to the AC connector and tighten the swivel nut.
Remove the dustproof cover from the Grid&EPS
10
port.
Click!
145