EN |
DIP1
DIP2
Setting
(bottom)
(top)
right
right
3-phase, earth monitor-
(OFF)
(OFF)
ing on
left (ON)
right
3-phase, earth monitor-
(OFF)
ing off
right
left (ON)
single-phase, earth
(OFF)
monitoring on
left (ON)
left (ON)
single-phase, earth
monitoring off
Setting the charging current
WARNING
Set the charging current configuration with the Wall-
box in a voltage-free state only.
Fig. 16: Rotary switch
e
Use a 0.02 in x 0.08 in screwdriver to adjust
the charging current of the Wallbox on the rotary
switch in accordance with the fuse of the build-
ing and with the rated power of the Wallbox.
g (Fig. 16)
36
Position
Value
F
32 A
E
30 A
D
25 A
C
20 A
B
16 A
A
15 A
9
13 A
8
10 A
7
8 A
6
6 A
2 and 3
Reset Wallbox to fac-
tory settings
To be able to charge,
afterwards set the
switch to the recently
determined maximum
possible charging cur-
rent
All other positions
Reserved for future ap-
plications
Connecting to the network
Connect Ethernet cable (optional)
1. Mount connector to the Ethernet cable.
2. Insert into the port from below.
Damage to the Wallbox
CAUTION
Leaks can be prevented if the plug is crimped inside
the Wallbox only.
Completing the assembly
Mount the cover
1. Fit and press down cover with integrated foam
seal.
2. Insert and tighten the 5x20 T25 screw at the
lower edge of the cover.