100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
Battery Charger
The LEDs on the battery charger indicate whether the charger has
120VAC power, if there is a battery fault and the charger state.
Battery charger rating 24 VDC 7 A.
RECOGNIZED
COMPONENT
MODEL / MODÈLE / MODELO #102652
XXXXXXX
Certified to CSA Std. C22.2 NO.107.2
NO. DE SERIE
Conforms to UL Std.1236
LED
SYMBOL
Artwork Notes
2mm safe margin; to be printed on White substrate.
This artwork belongs to Champion Power Equipment. The contents are confidential and privileged and shall not be disclosed to or used by or for
outside parties without the explicit consent of Champion Power Equipment.
E. O.
Green
Red
Yellow
Yellow
Yellow
No Yellow
AUTOMATIC BATTERY CHARGER
CHARGE AUTOMATIQUE DE BATTERIE
CARGADOR DE BATERÍA AUTOMÁTICO
For use with lead acid (LA/SLA), AGM, or Gel batteries.
Not for use with Lithium-ion batteries.
Pour une utilisation avec des batteries au
plomb-acide (LA / SLA), AGM ou gel.
Ne pas utiliser avec des batteries au lithium-ion.
Para uso con baterías de plomo ácido (LA/SLA), AGM o gel.
No para uso con las baterías de iones de litio.
INPUT: 80 - 125 VAC MAX 2.7 A 50/60 Hz
ENTRÉE : 80 - 125 VCA MAX 2,7 A 50 / 60 Hz
ENTRADA: 80 - 125 VCA MAX 2.7 A 50/60 Hz
OUTPUT: 24 VDC 7 A
SORTIE : 24 VCC 7 A
SALIDA: 24 VCC 7 A
SERIAL NO.
XXXXXXXXXXXX
N° DE SÉRIE
APN
4324-L-PR
Colors
Rev
A
DESCRIPTION
Size
Dieline by CPEC
K
Revision Changes
DC Voltage Adjustment - Preset
---
from the factory for proper DC
charger output. No adjustments
necessary.
Enforced Output - Press to charge
battery at maximum amperage for
a short period.
Power - Lit to indicate the charger
is receiving 120 VAC and is ready
to charge.
Fault or No Charge - Lit to indicate
a battery charging problem. If this
LED is lit, the LED on the aXis
Controller
, "LOW BATTERY" will
®
also be lit.
High Charge - Lit to indicate the
charger is operating above 50%
capacity. Trickle charge and mid
charge LED will also be lit.
Mid Charge - Lit to indicate the
charger is near 50% capacity.
Trickle charge LED will also be lit.
Trickle Charge - Lit to indicate the
battery is receiving a trickle charge.
Low Trickle Charge - When no
yellow LEDs are lit, the charger is in
low trickle charge state.
®
Emission Requirements
This engine-powered generator meets all United States
Environmental Protection Agency (EPA) Phase 3 requirements and
is approved for use in both the USA and Canada.
This generator is certified to operate on pipeline NG and LPG
(vapor) fuel for use as a stationary engine for standby power
generation. Federal and/or local laws may be violated if it is used
for any other purpose.
The maintenance schedule must be followed to ensure that the
engine complies with the applicable emission standards for the
duration of the engine's life.
For Emission control devices and systems, read and
understand your responsibilities for service as stated in the
Emission Control Warranty Statement of this manual.
24
GENERAL INfORMATION
NOTICE