100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
5. Clean the area around the spark plug to keep dirt out of the
engine and remove the spark plug.
6. Inspect the spark plug electrode and replace the plug if the
electrode shows signs of deterioration.
7. Check the gap before installing the spark plug. The spark
plug gap should be 0.024 – 0.035 in. (0.6 – 0.88 mm).
0.024 - 0.035 in.
(0.6 - 0.88 mm)
8. Carefully thread the spark plug into the engine and tighten to
20-30 N-m (14.8-22.1 lbf-ft).
9. Re-connect the spark plug cable.
10. Reinstall fuse removed in the earlier step.
11. Put the generator ON/OFF switch to the ON position.
12. Put the aXis Controller
®
MANUAL or AUTO for example).
Battery Maintenance
1. Turn the engine control module switch to the OFF position.
2. Inspect the battery cables and terminals for corrosion.
3. Check that the cables are securely fastened to the terminals.
4. Check the ground lug and make sure the connections are
tight.
5. Check the fluid level of the battery, unless sealed. If low, top
off the level using distilled water only.
Follow all battery instructions provided by the battery
manufacture.
to the previous position (either
®
Resetting the Maintenance Hour Meter
The maintenance hour meter counts down 100 hours. Once
completed the 100-hour maintenance, refer to below to reset the
hour meter.
Refer to the scheduled maintenance chart for specific
maintenance.
1. Locate the aXis Controller
2. Press OFF to take the generator off standby allowing you to
enter setting mode.
3. Press and hold
4. Cycle through until you reach maintenance hours (H) by
pressing the
button. Look for the maintenance icon to
be highlighted, lower right. Example shows 0 hours left for
maintenance. Time for reset the count down clock.
31
MAINTENANCE
.
®
for five (5) seconds to enter setting mode.