Descargar Imprimir esta página

Champion Global Power Equipment 100304 Manual Del Operador página 26

Generador doméstico de reserva de 22-kw con axis controller
Ocultar thumbs Ver también para 100304:

Publicidad

Idiomas disponibles

Idiomas disponibles

100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
fuel System
The engine is fitted with a dual master mixer assembly carburetion
system, which allows it to run on either NG or LPG. It has been
configured at the factory to run on NG. If your installation requires
the engine to run on LPG, orifices in the master mixer assembly
carburetor must be changed.
Battery Requirements
Two (2) 12 volt Group 26 batteries with maximum overall
dimension (L x W x H) 8 3/16 x 6 13/16 x 7 3/4 inches / 208 x 173
x 197 mm with an Automotive (A) post or terminal configuration.
Purchase batteries locally.
The recommended battery type for typical use is 540 CCA (Cold
Cranking Amps). However, a 525 CCA battery shown in the
"Recommended Battery Type" chart may be used for typical use,
if in a regularly warmer climates.
Alternatively, you may also use two (2) 12 volt Group 26R, but both
batteries must be 26R.
Recommended Battery Type
°F
-40
-4
°C
-40
-20
Ambient temperature
Install positive cable first. Install the battery series cable from the
positive (+) terminal of one battery to the negative (–) terminal of
the other battery. Always connect the positive (+) battery cable to
the generator first.
to starter
To starter
Battery Series Cable
540 CCA min
525 CCA min
32
68
104+
0
20
40+
to ground
To ground
®
For battery installation, maintenance, and safety requirements
refer to battery manufacturer's battery installation and safety
manual.
Battery Charging
The generator is equipped with an automatic battery charger. The
charger will sense the battery's state of charge and automatically
charge the battery when required. LED lights on the charger
display the battery state of charge.
26
GENERAL INfORMATION
Automotive
Post Style
Group size 26
CAUTION

Publicidad