100304 - 22-kW HOME STANDBY GENERATOR WITH AXIS CONTROLLER
9. After the oil is drained, reinstall the oil drain hose cap by
screwing it back on snugly, making sure o-ring is in place.
Pull the oil drain hose back into the HSB enclosure, and reclip
oil drain hose back on the oil hose clamp that was holding it.
10. Reinstall oil drain cap on the HSB enclosure front.
11. Fill the engine with the proper amount of engine oil.
12. Reinstall fuse removed in the earlier step.
13. Put the generator ON/OFF switch to the ON position.
14. Put the aXis Controller
®
MANUAL or AUTO for example).
Inspect and Clean Engine Air Cleaner
1. Press the OFF button on the aXis Controller
2. Remove the fuse from the front of the aXis Controller
will disable automatic starting in the event of a power outage.
3. Put the generator ON/OFF switch to the OFF position.
4. Unscrew the air filter screw cap holding the air cleaner cover
in place and remove the air cleaner cover. Check the air
cleaner gasket is in good shape, if not replace the gasket.
to the previous position (either
.
®
®
5. Remove the paper element/ foam filter.
B
C
E
A. Air Filter Screw
Cap
D. Paper element/ Foam
Filter
6. Inspect the foam filter and paper element for any rips or
tears. Replace if necessary.
7. Remove the foam filter from the paper element. Wash in liquid
detergent and water. Squeeze thoroughly dry in a clean cloth.
Saturate in clean engine oil. Squeeze in a clean, absorbent
cloth to remove all excess oil.
8. Hold the paper element up to a light. You should be able
to see light through the paper element, if not replace the
element. Inspect inside the air cleaner cover and base,
remove any dirt or debris.
9. Install foam filter on the paper element and place into the air
cleaner base.
10. Install the cover, gasket and screw the cap in place.
11. Reinstall fuse removed in the earlier step.
. This
®
12. Put the generator ON/OFF switch to the ON position.
13. Put the aXis Controller
MANUAL or AUTO for example).
Spark Plug
1. Press the OFF button on the aXis Controller
2. Remove the fuse from the front of the aXis Controller
will disable automatic starting in the event of a power outage.
3. Turn the generator ON/OFF switch to the OFF position.
4. Remove the spark plug cable from the spark plug.
30
A
D
B. Air Cleaner
Cover
E. Air Cleaner Base
to the previous position (either
®
MAINTENANCE
C. Air Cleaner
Gasket
®
.
. This
®