ENGLISH
Double pump mode: Setting when first used
1
1a
LC display
After switching on the module, all symbols appear on the display for 2 s. Next,
X
the menu
appears.
1a
The symbol
MA
(= master) blinks on the display of both pumps.
The left-hand pump in the direction of flow must be confirmed as master
pump
(see FIG. 1a)
.
If no setting is made, both pumps will run at a constant speed.
Setting the master pump:
Press acknowledge button of the master pump to confirm it
as master. The status is indicated on the display of the master
pump.
The other pump automatically becomes the slave.
'SL' (= slave) appears on the display of the slave pump.
For correcting a wrong setting, see the service menu