Commissioning
6.1
Basic settings via DIP switch
Changes made via the DIP switches only
take effect after restarting the product.
u Disconnect product from voltage if necessary.
6.1.1 Configuring the product
The tasks described in this section may only
be carried out by a qualified electrician.
In the top section of the housing, there are two 8-
pin DIP switches, with which the device can be con-
figured. In the delivery state, all DIP switches are
switched off ("OFF"). On delivery, the product is
ready for connection.
Fig. 11: DIP switches (delivery state)
1
Bank S1
2
Bank S2
Note the label on the housing.
The following functions can be set via the DIP
switches:
18
8 7 6 5 4 3 2 1
Bank S1
DIP
Function
switche
s
1
LED status display colour scheme
n "OFF":
n "Standby" operating state = blue
n "Charging" operating state =
n "ON":
n "Standby" operating state =
n "Charging" operating state =
2
Unbalanced load limitation
n "OFF": Unbalanced load limitation off
n "ON": Unbalanced load limitation on
3
Authorisation
n "OFF": No authorisation (Autostart)
n "ON": Authorisation via enable input
4, 5, 6,
No function
2
7, 8
Bank S2
1
DIP
Function
switch
1, 2, 3
Max. charging current
4, 5
Reduced charging current when down-
grade input is energised
6,7,8
Without function
6.1.2 Setting the maximum charging current
The tasks described in this section may only
be carried out by a qualified electrician.
The maximum charging current of the charging
point can be set via DIP switches 1, 2 and 3 on bank
S2.
green
green
blue