Descargar Imprimir esta página

Mennekes AMTRON 4You 100 11 Manual De Instrucciones Y De Instalación página 51

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 63
AMTRON® 4You 100 22
The maximum charging current can be set to 6 A,
10 A, 13 A, 16 A, 20 A, 25 A or 32 A.
DIP switch setting (bank S2)
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
The ON - ON - ON settings are invalid for configur-
ing the maximum charging current (the upper LED
of the LED status display lights up red).
AMTRON® 4You 100 11
The maximum charging current can be set to 6 A,
10 A, 13 A or 16 A.
DIP switch setting (bank S2)
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
The ON - ON - ON settings are invalid for configur-
ing the maximum charging current (the upper LED
of the LED status display lights up red).
6.1.3 Set unbalanced load limitation
The tasks described in this section may only
be carried out by a qualified electrician.
Max. char-
ging cur-
3
rent [A]
OFF
32
OFF
25
OFF
20
OFF
16
ON
13
ON
10
ON
6
Max. char-
ging cur-
3
rent [A]
OFF
16
OFF
16
OFF
16
OFF
16
ON
13
ON
10
ON
6
Unbalanced load refers to the uneven loading of
the phases of a three-phase alternating current net-
work. In Germany, for example, the maximum differ-
ence between two phases at the mains connection
point is 20 A (in accordance with VDE-N-AR-4100).
u Observe applicable national regulations.
u Set DIP switch 2 on bank S1 to "ON".
ð The unbalanced load is limited to 20 A (default
setting).
To limit the unbalanced load to a different current
value, the configuration tool is required.
1 "6.5 Description of the configuration tool"
[} 22]
6.2
Use cases
6.2.1 Downgrade
The tasks described in this section may only
be carried out by a qualified electrician.
If the maximum mains supply current is not avail-
able under certain circumstances or at certain
times, the charging current can be reduced by us-
ing the downgrade input. For example, the down-
grade input can be controlled by the following cri-
teria or control systems:
n Electricity rate
n Time
n Load shedding
n Manual control
n External load management
In the delivery state, the downgrade input is con-
trolled as follows:
Switching contact
Downgrade status
status
open
Downgrade inactive
closed
Downgrade active
The configuration tool is required to change the lo-
gic of the downgrade input.
EN
19

Publicidad

loading