1. POWER THE CONTROLLER
2. DISPLAY ALTERNATELY SHOWS "IL" AND "- - -"
3. ENTER "IL" PARAMETER MAINS C.T. RATIO (e.g. w/ C.T. 200/5 enter 40)
4. "+" AND "-" TO CHANGE THE PARAMETER AND "DATA" KEY TO
CONFIRM
5. "FAS" DISPLAYED IN TURN WITH "0" OR "1"
6. IS THE CONTROLLER INSTALLED ON A DUCATI ENERGIA POWER
FACTOR CORRECTION SYSTEM?
7. DISPLAY ALTERNATELY SHOWS "COS" AND THE SYSTEM POWER
FACTOR
8. STEPS SWITCHED IN AND OUT OF SERVICE TO ACHIEVE DESIRED
POWER FACTOR
9. STEPS SWITCHED IN AND OUT THREE TIMES (AUTO-ACQUISITION)
10. DISPLAY ALTERNATELY SHOWS "C1" AND THE VALUE MEASURED FOR
THE FIRST BANK
11. PRESS "DATA" KEY TO DISPLAY VALUE OF SUBSEQUENT BANKS
12. ARE THE MEASURED POWERS CORRECT?
13. PRESS THE "DATA" KEY THREE TIMES TO EXIT
14. START A NEW SELF-ACQUISITION OR CARRY OUT A MANUAL
PROGRAMMING
15. TO LAUNCH A NEW AUTO-ACQUISITION PROCEDURE PRESS "ALARM/
RESET" + "+"
16. FOR MANUAL PROGRAMMING PRESS "ALARM/RESET" + "-"
17. DISPLAY SHOWS "Pro" PRESS "+" OR "-" TO SET THE DESIRED
PROGRAM (SEE TABLE 1 - PAGE 72)
18. PRESS THE "DATA" KEY
19. DISPLAY SHOWS "PPC" PRESS "+" OR "-" TO SET THE VALUE OF THE
FIRST BANK
20. PRESS THE "DATA" KEY
53