NOTE: if the incoming current is insufficient (less than 200mA),
REGO cannot determine its direction and will stand by in this
status until current is supplied.
If the controller is installed on a DUCATI ENERGIA automatic
power factor correction system (pre-programmed controller),
no type of setting will be required and the controller will be ready
for perfect operation: it will alternately display "COS" and the power
factor of the system.
Ex.
7.3 If the controller is not installed on a DUCATI ENERGIA
automatic power factor correction unit (virgin controller), after
displaying the "FAS" parameter it will automatically launch the
automatic procedure for acquiring the powers of the single
capacitor steps. The capacitor steps will be switched on and
measured in sequence a total of three times each. At the end of
this procedure the controller will alternately display "C1" and the
measured power value of the first step; the power of the next step
can be displayed by pressing the DATA key.
Ex.
If the power measurements are incorrect, from the same menu
the user can press:
ALARM/RESET + L to launch a new autoacquisition procedure
–
ALARM/RESET + M to enter the manual programming mode (see
–
chap.10.8 - Page 68)
63