PARAMETER
Fan
REGO7-12
t1
t2
HU
StH
Adr
bdr
90
DESCRIPTION
Temperature threshold (°C)
for tripping fan activation.
Time (in seconds) of unavailability
of a step for re-activation. Always wait for
capacitors to discharge before switching
them back on.
Delay time (in units: each unit corresponds
to 500mS) between the activation
of one step and the next.
Mains VT transformation ratio.
Setting of trip time
of t.h.d. harmonic
distortion alarm.
Address of the instrument in the Rs485
serial connection with external units.
Speed of data transmission
through the Rs485 port
(Baud rate).
Table 3: Hidden menu parameters
RANGE
DEFAULT
5...50
25
5...255
30
1...600
2(=1S)
1...1000
1
1.2.3
-/-
1...99
1
1200...9600
9600