Ducati Energia REGO 5 Manual De Instrucciones página 70

Regulador automático de potencia reactiva
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

no = no acquisition procedure will be carried out.
AUt = a new automatic acquisition procedure will be carried out.
The capacitor steps will be switched on and measured in
sequence a total of three times each. At the end of this procedure
the controller will alternately display "C1" and the measured power
value of the first step; the power of the next step can be displayed
by pressing the DATA key.
Press DATA for three seconds to go on to the next parameter.
Pr = the switching logic and power of the single steps is manually set.
When the letters "Pro" appear, select the desired program (see
Table 1 - Page 72) using the L or M key and press DATA to confirm.
Thereafter, when the letters "PFC" appear, set the value in kVAr
of the first power factor correction capacitor bank (always
connected to output terminal "1"), again using the L or M key;
Example: if you have an automatic 100kVAr system with power
69

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rego 7Rego 12

Tabla de contenido