– ON status: this has the functions described previously, except that
the auto-reset (A.r.) function will not be active and the controller will
remain in a standby status until you press the ALARM/RESET key
on the front panel. Pressing this key will enable the controller to
resume normal operation.
– OFF status: the protection and alarm or signaling function and all
their consequent actions are completely inhibited. The user should
be fully aware of the risks of choosing the OFF status; as a rule it is
an unadvisable choice, since it may give rise to potentially
hazardous situations.
– A.r. status (auto-reset-default status): it has the functions described
previously.
When the controller is turned on for the first time, the default status of
all alarms is A.r.
To access the menu, press AUTO/MAN + L; the letters "ALP" will
appear and the L LED will flash.
Press the corresponding key to access the settings. The s and M LEDs
will flash and the first alarm/signal will be displayed; to change the
alarm status press the L or M key and to go on to the next alarm
press the DATA key (
been displayed, press the DATA key again to exit the function.
14) HIDDEN MENU
Some REGO parameters are present in the hidden menu. These
settings may be accessed by the user only when setting the C.T. ratio.
°
C, UFF, thd, COS); after the last parameter has
87