Generator Power Factor Correction Mode - Ducati Energia REGO 5 Manual De Instrucciones

Regulador automático de potencia reactiva
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

regardless of the current controller situation ("tSt" will appear on the
display and the AUTO/MAN LED will flash);
if the procedure is launched during normal operation, it will be
necessary to press the AUTO/MAN key for about another 2 seconds
to confirm the launching of the test. The procedure consists in switching
on the individual steps in sequence at two-second intervals. The closing
time of an individual step is five seconds.

12.8 GENERATOR POWER FACTOR CORRECTION MODE

To correct the power factor of the generators, the user must set this
operating mode, which involves inhibiting the automatic mains CT
direction adjustment function and configuring the signals accordingly.
This operation must be carried out with the mains powered by the
generator.
Press AUTO/MAN + M to access the menu for fixing the C.T. direction.
When you press the keys, the M LED will flash and you must press the
corresponding key. At this point the L and M LEDs will flash and the
controller will simultaneously display "Inu" (INV) in turn with "On" or
"OFF".
To set the appropriate operating mode for correcting the power factor
of generators, press the L key: the word "On" will appear. If, on the
contrary, you wish to enable the C.T. direction auto-adjustment function
80